Plan Review Notes
Plan Review Notes For Permit 19030941
Permit Number 19030941
Review Stop P
Sequence Number 1
Notes
Date Text
2019-03-29 14:44:391) SUBMIT A COPY OF THE UL 142 CERTIFICATION FOR THE
 FUEL TANK.WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT DETAILS FOR THE TYPE OF ENCLOSURE FOR THE
 GENERATOR.WPB AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT A COPY OF THE APPROVAL FROM THE PALM BEACH
 COUNTY DEPARTMENT OF ENVIRONMENTAL RESOURCE MANAGEMENT
 FOR THE FUEL TANK AND COMPLIANCE WITH PALM BEACH COUNTY
 ORDINANCE 2015-008.
 4) SUBMIT DETAILS AS TO HOW THE GENERATOR IS PROTECTED
 AGAINST UNAUTHORIZED ACCESS, TAMPERING AND TRESPASSING.
 NFPA 30 SEC. 15.3.6, WPB AMEND. TO FBC SEC. 107.2.1.
 5) SUBMIT SPECIFICATIONS ON THE FUEL TANK SHOWING
 COMPLIANCE WITH NFPA 30.
 6) INDICATE THE CLASSIFICATION OF COMBUSTIBLE LIQUID OF
 THE DDIESEL FUEL ( CLASS II, IIA, CLASS III, IIIA, )
 PER NFPA 30 SEC. 4.3.2.
 7) SUBMIT DETAILS FOR THE NORMAL VENTING AND EMERGENCY
 VENTING OF THE FUEL TANK. VENT PIPING SHALL COMPLY WITH
 NFPA 30 SEC. 27.8.
 8) THE FUEL TANK VENTS SHALL BE 5 FEET FROM ANY
 BUILDING OPENINGS AND 15 FEET FROM POWERED VENTILATION
 AIR INTAKES PER NFPA 30-12 SEC.19.5.3.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW