 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR, FUEL PIPING, ENGINE EXHAUST PIPE, MUFFLER,
 AND ALL OTHER ASSOCIATED SYSTEM COMPONENTS- SECTION
 304.1 FBC M.
  
 2) SUBMIT THE UL 2200 CERTIFICATE OF COMPLIANCE FOR THE
 GENERATOR- SECTION 915.1 FBC M. THE MANUFACTURER'S
 SPECIFICATIONS AND/OR UL CERTIFICATE SHALL INDICATE THE
 GENERATOR IS IN COMPLIANCE WITH NFPA 37.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FUEL
 TANK THAT INCLUDES THE TANK'S UL LISTING- UL 142 OR UL
 2085- SEE SECTION 21.4.2.1.1 NFPA 30.
  
 4) PROVIDE AN EXHAUST PIPE DIAGRAM SHOWING THE TOTAL
 SYSTEM RUN AND LENGTH MEASUREMENT, AND TERMINATION
 LOCATION, AND CLEARANCE DISTANCES GRAVITY OR MECHANICAL
 AIR INTAKES INTO THE BUILDING PLEASE INCLUDE ALL
 COMPONENTS OF THE SYSTEM INCLUDING THE SILENCER.- SEE
 SECTION 8.1- 8.4 NFPA 37, AND SECTION 501.3.1 FBC M.
  
 5) PROVIDE DETAILS AND SPECIFICATIONS FOR NORMAL AND
 EMERGENCY RELIEF VENTING OF THE TANK, INCLUDING VENT
 PIPING RUNS AND TERMINATION LOCATIONS- SECTION 24.13
 NFPA 30.
  
 6) PROVIDE WIND LOAD ENGINEERING FOR ATTACHMENT OF THE
 GENERATOR TO THE ROOF STRUCTURE- SECTION 301.15 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  