| Notes |
| Date |
Text |
| 2019-04-18 15:13:27 | UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF | | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS. | | | MANUFACTURER SPECS SHALL PROVIDED FOR GENERATOR TO BE | | | INSTALLED. | | | GENERATOR IS TO BE TESTED IN COMPLIANCE WITH CHAPTERS 7 | | | & 8 OF NFPA 110. | | | ADDITIONALLY, LOAD TEST PAPERWORK SHALLL BE REQUIRED | | | UPON CALLING IN FOR A LOAD TEST. | | | | | | S. THOMAS | | | 561-804-4728 |
|