2019-04-18 15:13:27UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
 MANUFACTURER SPECS SHALL PROVIDED FOR GENERATOR TO BE
 INSTALLED.
 GENERATOR IS TO BE TESTED IN COMPLIANCE WITH CHAPTERS 7
 & 8 OF NFPA 110.
 ADDITIONALLY, LOAD TEST PAPERWORK SHALLL BE REQUIRED
 UPON CALLING IN FOR A LOAD TEST.
  