Plan Review Notes
Plan Review Notes For Permit 19030941
Permit Number 19030941
Review Stop E
Sequence Number 1
Notes
Date Text
2019-04-05 13:00:06ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE OF THE WORK SHOWN IS TOO LOW, PLEASE SUBMIT A
 BREAK DOWN OF ALL EQUIPMENT AND LABOR FOR THE TOTAL JOB
 INSTALATION.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO
 INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. FINAL
 BUILDING PERMIT VALUATION
 SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) PLANS SHOW TWO EXISTING GENERATORS STAYING OR DEMO?
  
 3) CUT SHEETS FOR ALL EQUIPMENT INVOLVED WITH THIS
 INSTALLATION.
  
 4) PAGE E-1.1 COLOR CODE FOR HIGH VOLTAGE NEEDS TO BE
 CHECKED WITH THE EXISTING AND IS TO MATCH EXISTING
 COLOR CODE USED IN THE BUILDING.
  
 5) E-2 NEW FAULT CURRENT VALUES ARE SHOWN HOW WHERE
 THEY CALCULATED PLEASE SHOW.
  
 6) ATS AND GENERATOR HAVE BREAKERS THAT CAN OR ARE SET
 AT 1200 AMPERES THEY SHALL MEET THE REQUIREMENTS 240.87
  
 240.87 ARC ENERGY REDUCTION
 WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR
 WHICH THE ACTUAL OVERCURRENT DEVICE INSTALLED IN A
 CIRCUIT BREAKER IS RATED
 OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND
 (B) SHALL APPLY.
  
 (A) DOCUMENTATION. DOCUMENTATION SHALL BE AVAILABLE TO
 THOSE AUTHORIZED TO DESIGN, INSTA LL, OPERATE, OR
 INSPECT THE INSTALLATION
 AS TO THE LOCATION OF THE CIRCUIT BREAKER(S).
 (B) METHOD TO REDUCE CLEARING TIME. ONE OF THE
 FOLLOWING OR APPROVED EQUIVALENT MEANS SH ALL BE
 PROVIDED:
 (1) ZONE-SELECTIVE INTERLOCKING
 (2) DIFFERENTIAL RELAYING
 (3) ENERGY-REDUCING MAINTENANCE SWITCHING WITH LOCAL
 STATUS INDICATOR
 (4) ENERGY-REDUCING ACTIVE ARC FLASH MITIGATION SYSTEM
 (5) AN APPROVED EQUIVALENT MEANS
  
 7) PAGE E-6 WIRE SCHEDULE FOR #1 SHOWS 3-#10, 1-18-2 C,
 AND 1- CAT 5 PLEASE EXPLAIN.
  
 8) PAGE E-7 SIGNS NEED TO HAVE ONE THAT MEETS 445.11.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE CITY RESUBMITTAL FORM. ADDITIONALLY, INSERT
 CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED
 SHEETS.