Plan Review Notes
Plan Review Notes For Permit 19030940
Permit Number 19030940
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-12 10:31:341) SHT. A-1.0 - THE DOOR FOR TOILET ROOMS #108 & #109
 CANNOT SWING INTO THE CLEAR FLOOR SPACE FOR THE
 LAVATORY OR THE WATER CLOSET. 2017 FBC-ACCESS. SEC.
 603.2.3.
 2) DRINKING FOUNTAINS ARE REQUIRED IN THIS SPACE PER
 2017 FBC-PLUMBING TABLE 403.1 & 410.3. SHOW THE
 LOCATION OF THE REQUIRED DRINKING FOUNTAINS ON THE
 ARCHITECTURAL FLOOR PLAN AND ALSO ON THE PLUMBING PLANS
 AND WATER AND SANITARY RISERS. 2017 FBC-PLUMBING TABLE
 403.1 & WPB AMEND. TO FBC 107.2.1.
 3) A SERVICE SINK IS REQUIRED IN THIS SPACE PER 2017
 FBC-PLUMBING TABLE 403.1. SHOW THE LOCATION OF THE
 SERVICE SINK ON THE ARCHITECTURAL FLOOR PLAN AND
 PLUMBING PLAN AND SANITARY AND WATER RISERS.
 4) A LINT INTERCEPTOR IS REQUIRED FOR THE WASHING
 MACHINE PER 2017 FBC-PLUMBING SEC.1003.6.
 5) SHT. A-4.0 - DETAIL #3 - ELEVATION - "A" - THE
 TOILET PAPER DISPENSER SHALL BE LOCATED A MINIMUM OF 7
 INCHES AND A MAXIMUM OF 9 INCHES TO THE CENTER OF THE
 DISPENSER FROM THE FRONT OF THE TOILET BOWL.2017
 FBC-ACCES. SEC.604.7.
 6) SHT. P-0 - THE WASHING MACHINE SHALL BE INSTALLED ON
 A MINIMUM 3 INCH STACK. SHOW THIS ON THE PLAN. 2017
 FBC-PLUMBING SEC.406.2.
 7) THE WATER SUPPLY VALVES AT THE WASHING MACHINE BOX
 SHALL BE ACCESSIBLE PER FBC-PLUMBING SEC.606.3.
 8) TEMPERED WATER IS REQUIRED AT THE LAVATORIES PER
 FBC-PLUMBING SEC.416.5.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  