2019-04-26 12:34:41****CORRECTIONS****
 W.P.B. PERMIT: 19030940
 REVIEWED: APRIL 26, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) PLEASE REVIEW EGRESS FROM CARE ROOM 104 AND THE
 CORRIDOR LEADING TO EXIT DISCHARGE. THESE COMMENTS ARE
 IN PARALLEL WITH FIRE AND THE MOST RESTRIVTIVE WILL
 APPLY.
  
 466.8 FBC[B] CORRIDORS. EVERY INTERIOR CORRIDOR SHALL
 BE CONSTRUCTED OF WALLS HAVING NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE RATING. EXCEPTIONS:
 A. IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTIONS 901.6 AND 903.3.1.1 CORRIDOR WALLS SHALL
 NOT BE REQUIRED TO BE RATED, PROVIDED THAT SUCH WALLS
 FORM SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 710.
 B. WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A
 1-HOUR FIRE-RESISTANCE RATING WHERE TESTED AS A WALL,
 THE CORRIDOR WALLS SHALL BE PERMITTED TO TERMINATE AT
 THE CORRIDOR CEILING.
 C. LAVATORIES IN UNSPRINKLERED BUILDINGS SHALL NOT BE
 REQUIRED TO BE SEPARATED FROM CORRIDORS, PROVIDED THAT
 THEY ARE SEPARATED FROM ALL OTHER SPACES BY WALLS
 HAVING NOT LESS THAN A 1-HOUR FIRE-RESISTANCE RATING IN
 ACCORDANCE WITH SECTION 709.
 D. LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED
 FROM CORRIDORS, PROVIDED THE BUILDING IS PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTIONS 901.6 AND
 903.3.1.1.
  
 1020.1 FBC[B] CONSTRUCTION. CORRIDORS SHALL BE
 FIRE-RESISTANCE RATED IN ACCORDANCE WITH TABLE 1020.1.
 THE CORRIDOR WALLS REQUIRED TO BE FIRE-RESISTANCE RATED
 SHALL COMPLY WITH SECTION 708 FOR FIRE PARTITIONS. (SEE
 1020 FOR EXCEPTIONS)
  
 1020.6 FBC[B] CORRIDOR CONTINUITY.
 FIRE-RESISTANCE-RATED CORRIDORS SHALL BE CONTINUOUS
 FROM THE POINT OF ENTRY TO AN EXIT, AND SHALL NOT BE
 INTERRUPTED BY INTERVENING ROOMS. WHERE THE PATH OF
 EGRESS TRAVEL WITHIN A FIRE-RESISTANCE-RATED CORRIDOR
 TO THE EXIT INCLUDES TRAVEL ALONG UNENCLOSED EXIT
 ACCESS STAIRWAYS OR RAMPS, THE FIRE-RESISTANCE RATING
 SHALL BE CONTINUOUS FOR THE LENGTH OF THE STAIRWAY OR
 RAMP AND FOR THE LENGTH OF THE CONNECTING CORRIDOR ON
 THE ADJACENT FLOOR LEADING TO THE EXIT. EXCEPTIONS:
 A. FOYERS, LOBBIES OR RECEPTION ROOMS CONSTRUCTED AS
 REQUIRED FOR CORRIDORS SHALL NOT BE CONSTRUED AS
 INTERVENING ROOMS.
 B. ENCLOSED ELEVATOR LOBBIES AS PERMITTED BY ITEM 1 OF
 SECTION 1016.2 SHALL NOT BE CONSTRUED AS INTERVENING
 ROOMS.
  
 2) 402.1 FBC[A] PROVIDE ACCESSIBLE ROUTE FROM PARKING
 LOT. IN ADDITION TO ACCESSIBLE ENTRANCES REQUIRED BY
 SECTIONS 1105.1.1 THROUGH 1105.1.7 (PARKING GARAGE
 ENTRANCES, ENTRANCES FROM TUNNELS OR ELEVATED WALKWAYS,
 RESTRICTED ENTRANCES, ENTRANCES FOR INMATES OR
 DETAINEES, SERVICE ENTRANCES AND ENTRANCES TO TENANT
 SPACES, DWELLING UNITS AND SLEEPING UNITS), AT LEAST 60
 PERCENT OF ALL PUBLIC ENTRANCES SHALL BE ACCESSIBLE.
 SEE THE EXCEPTIONS FOR ENTRANCES TO AREAS NOT REQUIRED
 TO BE ACCESSIBLE AND LOADING/SERVICE ENTRANCES THAT ARE
 NOT THE ONLY TENANT SPACE ENTRANCE.
 - PLEASE SHOW ACCESSIBLE ROUTE TO EXISTING DOOR THAT
 PROVIDES ACCESS TO NEW AREAS.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  