| 2019-04-26 12:34:41 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 19030940 |
| | REVIEWED: APRIL 26, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) PLEASE REVIEW EGRESS FROM CARE ROOM 104 AND THE |
| | CORRIDOR LEADING TO EXIT DISCHARGE. THESE COMMENTS ARE |
| | IN PARALLEL WITH FIRE AND THE MOST RESTRIVTIVE WILL |
| | APPLY. |
| | |
| | 466.8 FBC[B] CORRIDORS. EVERY INTERIOR CORRIDOR SHALL |
| | BE CONSTRUCTED OF WALLS HAVING NOT LESS THAN A 1-HOUR |
| | FIRE-RESISTANCE RATING. EXCEPTIONS: |
| | A. IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH SECTIONS 901.6 AND 903.3.1.1 CORRIDOR WALLS SHALL |
| | NOT BE REQUIRED TO BE RATED, PROVIDED THAT SUCH WALLS |
| | FORM SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 710. |
| | B. WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A |
| | 1-HOUR FIRE-RESISTANCE RATING WHERE TESTED AS A WALL, |
| | THE CORRIDOR WALLS SHALL BE PERMITTED TO TERMINATE AT |
| | THE CORRIDOR CEILING. |
| | C. LAVATORIES IN UNSPRINKLERED BUILDINGS SHALL NOT BE |
| | REQUIRED TO BE SEPARATED FROM CORRIDORS, PROVIDED THAT |
| | THEY ARE SEPARATED FROM ALL OTHER SPACES BY WALLS |
| | HAVING NOT LESS THAN A 1-HOUR FIRE-RESISTANCE RATING IN |
| | ACCORDANCE WITH SECTION 709. |
| | D. LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED |
| | FROM CORRIDORS, PROVIDED THE BUILDING IS PROTECTED |
| | THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| | SPRINKLER SYSTEM IN ACCORDANCE WITH SECTIONS 901.6 AND |
| | 903.3.1.1. |
| | |
| | 1020.1 FBC[B] CONSTRUCTION. CORRIDORS SHALL BE |
| | FIRE-RESISTANCE RATED IN ACCORDANCE WITH TABLE 1020.1. |
| | THE CORRIDOR WALLS REQUIRED TO BE FIRE-RESISTANCE RATED |
| | SHALL COMPLY WITH SECTION 708 FOR FIRE PARTITIONS. (SEE |
| | 1020 FOR EXCEPTIONS) |
| | |
| | 1020.6 FBC[B] CORRIDOR CONTINUITY. |
| | FIRE-RESISTANCE-RATED CORRIDORS SHALL BE CONTINUOUS |
| | FROM THE POINT OF ENTRY TO AN EXIT, AND SHALL NOT BE |
| | INTERRUPTED BY INTERVENING ROOMS. WHERE THE PATH OF |
| | EGRESS TRAVEL WITHIN A FIRE-RESISTANCE-RATED CORRIDOR |
| | TO THE EXIT INCLUDES TRAVEL ALONG UNENCLOSED EXIT |
| | ACCESS STAIRWAYS OR RAMPS, THE FIRE-RESISTANCE RATING |
| | SHALL BE CONTINUOUS FOR THE LENGTH OF THE STAIRWAY OR |
| | RAMP AND FOR THE LENGTH OF THE CONNECTING CORRIDOR ON |
| | THE ADJACENT FLOOR LEADING TO THE EXIT. EXCEPTIONS: |
| | A. FOYERS, LOBBIES OR RECEPTION ROOMS CONSTRUCTED AS |
| | REQUIRED FOR CORRIDORS SHALL NOT BE CONSTRUED AS |
| | INTERVENING ROOMS. |
| | B. ENCLOSED ELEVATOR LOBBIES AS PERMITTED BY ITEM 1 OF |
| | SECTION 1016.2 SHALL NOT BE CONSTRUED AS INTERVENING |
| | ROOMS. |
| | |
| | 2) 402.1 FBC[A] PROVIDE ACCESSIBLE ROUTE FROM PARKING |
| | LOT. IN ADDITION TO ACCESSIBLE ENTRANCES REQUIRED BY |
| | SECTIONS 1105.1.1 THROUGH 1105.1.7 (PARKING GARAGE |
| | ENTRANCES, ENTRANCES FROM TUNNELS OR ELEVATED WALKWAYS, |
| | RESTRICTED ENTRANCES, ENTRANCES FOR INMATES OR |
| | DETAINEES, SERVICE ENTRANCES AND ENTRANCES TO TENANT |
| | SPACES, DWELLING UNITS AND SLEEPING UNITS), AT LEAST 60 |
| | PERCENT OF ALL PUBLIC ENTRANCES SHALL BE ACCESSIBLE. |
| | SEE THE EXCEPTIONS FOR ENTRANCES TO AREAS NOT REQUIRED |
| | TO BE ACCESSIBLE AND LOADING/SERVICE ENTRANCES THAT ARE |
| | NOT THE ONLY TENANT SPACE ENTRANCE. |
| | - PLEASE SHOW ACCESSIBLE ROUTE TO EXISTING DOOR THAT |
| | PROVIDES ACCESS TO NEW AREAS. |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS. |
| | FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE |
| | REQUIRED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |