Plan Review Notes
Plan Review Notes For Permit 19030936
Permit Number 19030936
Review Stop E
Sequence Number 1
Notes
Date Text
2019-03-27 07:10:23ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PRODUCT DOES APPEAR TO BE UL LISTED OR LISTED BY
 ANOTHER NATIONALLY RECOGNIZED TESTING LABORATORY
 (NRTL). SPEC SHEET IS FROM 2014. "MEETS OR EXCEEDS THE
 FOLLOWING SPECIFICATIONS" DOES NOT MEAN IT HAS BEEN
 LISTED. PROVIDE LISTING. FBC 107.2.1 NEC
 90.7,110.2,110.3B
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  