Plan Review Notes
Plan Review Notes For Permit 19030921
Permit Number 19030921
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-02 14:56:13PLUMBING 1ST REVIEW**DENEIED**
  
 1) PROVIDE A SANITARY RISER ISOMETRIC DRAWING. FBC
 107.3.5
  
 2) IS THE 3 PIECE SHOWER DRAIN MADE BY KBRS FOR THERE
 SYSTEM? IF NOT PROVIDE PRODUCT SUPPORT DOCUMENTS THAT
 ALLOW THE USE OF A LIQUID LINERS ON THE MANUFACTURES
 DRAIN ASSEMBLY. FBC 107.2.1
  
 3) PERSON DESIGNING PLANS SHALL SIGN AND DATE TAKING
 RESPONSIBILITY. F.S 471
  
 4) PROVIDE SHOWER VALVE MANUFACTURE MANUALS SHOWING
 THEY ARE ASSE 1016 APPROVED BEING PRESSURE BALANCED,
 THERMOSTATIC OR A COMBINATION OF BOTH AND HAVE A LIMIT
 STOP OF 120F. FBC P 417
  
 TIM HUNT
 PLUMBING PLANS EXAMINER