| 2019-05-16 11:37:38 | SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | SEC. 801.3 FBC-EXISTING BUILDING. |
| | |
| | |
| | 1- THERE IS A NOTE ON THE ENLARGEMENT DETAIL 1 ON SHEET |
| | S200 STATING "EXISTING LIGHT GAUGE WALLS TO REMAIN. ANY |
| | WALL THAT REQUIRED TO INSTALL THE NEW STEEL FRAMING |
| | SHALL BE BUILT BACK PER THE ORIGINAL BASE BUILDING |
| | DRAWINGS". |
| | ENGINEER OF RECORD NEEDS TO PROVIDE COMPLETE DETAILS |
| | AND SPECIFICATIONS FOR THE FRAMING OF THE WALL THAT IS |
| | GOING TO BE BUILT TO RECEIVE THE NEW STOREFRONT. SEC. |
| | 1609.1 FBC. |
| | |
| | RESPONSE: |
| | RESPONSE LETTER FROM MCNAMARA/SLAVIA, INC. STATES THAT |
| | "THE STOREFRONT SYSTEM SPANS VERTICALLY AND IS ATTACHED |
| | TO THE SLAB ON GRADE AT THE BASE AND A NEW HSS MEMBER |
| | AT THE HEAD PER SECTION 1/S320. THE LIGHT GAUGE WALLS |
| | ARE INFILL EXTERIOR WALLS ONLY AND THEIR DESIGN IS BY |
| | THE LIGHT GAUGE ENGINEER". |
| | |
| | THIS STATEMENT DOESN'T SEEM TO BE CORRECT. ACCORDING TO |
| | STOREFRONT PRODUCT APPROVAL AND DETAILS SUBMITTED THE |
| | STOREFRONT IS ATTACHED TO THE SIDE WALLS AS WELL. ALSO, |
| | THERE WERE NO DETAILS AND SPECIFICATIONS SUBMITTED FROM |
| | THE LIGHT GAUGE ENGINEER. |
| | PROVIDE COMPLETE INFORMATION. |
| | NOTE: COORDINATE WITH STOREFRONT PRODUCT APPROVAL TO |
| | AVOID CONFLICTS/DELAYS. |
| | |
| | |
| | 2- WALL SECTIONS ON SHEET S320 NEED TO PROVIDE COMPLETE |
| | SPECIFICATIONS FOR THE CONSTRUCTION OF THE PARAPET. |
| | NEED TO SPECIFY THE GAUGE OF THE STEEL STUDS AND |
| | PROVIDE FASTENER SPECIFICATIONS. SEC. 1609.1 FBC. |
| | |
| | RESPONSE: |
| | |
| | RESPONSE LETTER FROM MCNAMARA/SLAVIA, INC. STATES THAT |
| | "THE FINAL DESIGN OF THE LIGHT GAUGE STUDS WILL BE A |
| | ""DIFFERENT SUBMITTAL"" SIGNED AND SEALED BY THE GC'S |
| | ENGINEER". |
| | |
| | THE DIFFERED SUBMITTAL WAS NOT SUBMITTED. PROVIDE |
| | COMPLETE INFORMATION. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR THE NEW STOREFRONT SYSTEM AND DOORS |
| | SPECIFIED ON PLANS. |
| | |
| | RESPONSE: |
| | RESPONSE LETTER FROM MCNAMARA/SLAVIA, INC. STATES THAT |
| | "PLEASE REFER TO ARCHITECTURAL SHEET A550 FOR TH |
| | STOREFRONT AND DOOR ASSEMBLIES. THEY MATCH THE |
| | PREVIOUSLY APPROVED NOA'S FOR THE BASE BUILDING". |
| | |
| | (A)PRODUCT APPROVALS SUBMITTED AND PRODUCT APPROVALS |
| | LISTED ON SHEET A550 DON'T MATCH. REVISE AS REQUIRED TO |
| | MATCH. |
| | |
| | (B) STOREFRONT ENGINEERED DRAWINGS SUBMITTED WITH THE |
| | DOORS AND STOREFRONT PRODUCT APPROVALS NEED TO HAVE THE |
| | ENGINEER'S (THOMAS J. TWOMEY) SEAL AND SIGNATURE AS |
| | REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING DOCUMENTS |
| | FOR PUBLIC RECORDS. ENGINEER DRAWINGS SUBMITTED |
| | NOTE: THIS IS A DIGITAL SUBMITTAL. NEED DIGITAL |
| | SIGNATURE ON DIGITAL SUBMITTALS. |
| | |
| | 4- OK. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |