2019-04-03 10:08:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. REVISION SHOWS A RECEPTACLE OUTLET IN THE POWDER
 BATH THAT IS NOT GFCI PROTECTED. PROVIDE CORRECTION.
 NEC 210.8; FBC RE E3902
 2. REVISION SHOWS A CHANDELIER IN THE MASTER WALK IN
 CLOSET. PER CODE, LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CORRECTION. NEC 410.16; FBC RE E4003.12
 3. REVISION SHOWS THE ADDITION OF SUB-PANEL D. WHAT IS
 THE LOCATION OF THIS PANEL? PROVIDE LOCATION FOR
 CONFIRMATION OF CODE COMPLIANCE. WPB FBC 107.2.1
 4. RISER DIAGRAM SHOWS TOO MANY WIRES IN FEED TO
 SUB-PANEL B. WHAT IS THE ADDITIONAL WIRE FOR? PROVIDE
 CLARIFICATION AND CORRECTIONS AS NEEDED. WPB FBC
 107.2.1
 5. RISER SHOWS THE ADDITON OF SUB-PANEL D, BUT THE LOAD
 CALCULATION HAS NOT BEEN UPDATED TO REFLECT THIS
 INFORMATION. PROVIDE CORRECTION. NEC 220; FBC RE
 E3602.2
 6. THE 2ND FLOOR BALCONY HAS BEEN CHANGED TO INCLUDE A
 STORAGE AREA. RECEPTACLE OUTLETS IN A STORAGE AREA
 REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8;
 FBC RE E3902
 7. REVISION SHOWS THE SMOKE/CO ALARM IN MASTER FED FROM
 A DIFFERENT CIRCUIT THAN OTHER ALARMS. CODE REQUIRES
 THAT ALL ALARMS ARE INTERCONNECTED. PROVIDE CORRECTION.
 FBC RE R314.4
 8. REVISION SHOWS THREE BATHROOMS ON CIRCUIT B-2 THAT
 FEEDS ALL LIGHTING AND RECEPTACLES IN THE BATHROOMS. A
 MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE
 CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
 9. COMMENT FOR VALUE REMOVED PER STEVE KENNEDY.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER