| Date |
Text |
| 2019-04-09 16:44:47 | 1ST REVIEW FBC-2017 MECHANICAL |
| | REVISION #19030907 |
| | 4/9/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SIGNATURE OF CONTRACTOR OR QUALIFIER ON PLANS |
| | REQUIRED: SEE FLORIDA STATUTE 633.021, AND SECTION |
| | 107.2.1 FBC. WPB AMENDMENTS TO THE FBC: ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | |
| | 2) SHOW THE CFMS AT EACH SUPPLY DIFFUSER AND EACH |
| | RETURN GRILL- SECTION R403.7.1 FBC EC. |
| | |
| | 3) PROVIDE A HATCH FOR ACCESS TO THE AIR HANDLER IN THE |
| | ATTIC- SEE SECTION M1305.1 FBC R AND SECTIONS R402.2.4& |
| | R403.3.6 FBC EC FOR COMPLAUINCE REQUIREMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |