| 2019-05-28 14:32:23 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 3RD REVIEW |
| | PLUMBING COMMEMTS: DENIED |
| | PLEASE NOTE THAT PLUMBING WILL NOT BE APPROVED UNTIL |
| | THE ISSUES ON THE ARCHITECTURAL PLANS HAVE BEEN |
| | CORRECTLY ADDRESSED |
| | |
| | 1. 3RD REQUEST- ARCHITECTURAL ISSUE: PLAN SHEET A6.0; |
| | THE LOCATION OF THE REAR GRAB BAR SHALL COMPLY WITH |
| | FBC-ACCESS. SEC.604.5.2. 24" OPPOSITE THE 12" NOT SHOWN |
| | ON DETAIL (GRAB BAR AT WATER CLOSET) SHT. A6.0. TO |
| | CLARIFY THE DETAIL, DIMENSION FROM CENTER OF WATER |
| | CLOSET TO LEFT SHALL BE 24? MIN., NOT 12?. |
| | |
| | 2. 3RD REQUEST-PLAN SHEET P-2: PLUMBING GENERAL NOTE #1 |
| | REFERS TO THE 2014 FBC. THE CODE IN EFFECT IS THE 2017 |
| | FBC. REVISE AND RESUBMIT. |
| | |
| | 3. 3RD REQUEST-PER WPB FBC 107.2.1, SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS FOR THE TANKLESS WATER |
| | HEATERS. |
| | |
| | 4. 2ND REQUEST- ARCHITECTURAL ISSUE: SHT. A6.0 DETAIL |
| | #9 SHOWS GRAB BARS MEASURED TO THE ESCUTCHEON RING; THE |
| | DETAIL FOR THE GRAB BARS AT WATER CLOSET SHOWS MEASURED |
| | TO THE CENTER OF THE GRAB BAR, THEY BOTH SHALL SHOW |
| | MEASURED TO THE TOP OF THE GRIPPING SURFACE. FBC ACC |
| | 609.4. PLEASE NOTE THAT DETAIL #7 BATHROOM BACKING |
| | DETAIL CORRECTLY SHOWS THE REQUIREMENTS. RECONCILE |
| | DETAIL #9 WITH #7. |
| | |
| | 5. REGARDING THE FOLLOWING COMMENTS MADE DURING THE |
| | SECOND REVIEW CONCERNING THE SHOWER IN THE TOILET RM W/ |
| | SHOWER STAFF RM #110, PLEASE NOTE: |
| | A. ARCHITECTURAL ISSUE: SHT. A6.0 DETAIL #5 THE |
| | ACCESSIBLE SHOWER DETAIL DOES NOT MATCH DETAIL #1 |
| | ENLARGED BATHROOM THE SHOWER SHALL COMPLY WITH FBC ACC |
| | 608.2.2.1, 608.3.2 , 608.5.2. NOTE THAT THE SPACE AND |
| | CONFIGURATION ALLOWED BY THE ARCHITECT DOES NOT MEET |
| | THE REQUIREMENTS FOR A STANDARD ROLL IN SHOWER |
| | COMPARTMENT. |
| | B. ARCHITECTURAL ISSUE: THE SEAT IS BEING SHOWN ON THE |
| | SAME SIDE AS THE END GRAB BAR IT SHALL BE ON THE |
| | OPPOSITE END IT WILL BE DIFFICULT TO COMPLY WITH THE |
| | ANGLE WALL. FBC ACC 608.3.2 |
| | C. ARCHITECTURAL ISSUE: THE ENDS OF THE GRAB BARS SHALL |
| | BE 6" MAX FROM ADJACENT WALL. FBC ACC 608.3.2 |
| | D. ARCHITECTURAL ISSUE: SHOW CLEAR FLOW SPACE FOR |
| | SHOWER. FBC ACC 608.2.2.1 |
| | |
| | 6. ADDITIONAL COMMENTS CONCERNING TOILET RM W/ SHOWER |
| | STAFF RM #110: |
| | A. ARCHITECTURAL ISSUE: FBC ACC 604.2 REQUIRES THAT THE |
| | WATER CLOSET POSITIONED WITH A WALL OR PARTITION TO THE |
| | REAR AND ONE SIDE OF THE FIXTURE; SIDE AND REAR HAND |
| | BARS SHALL CONFORM TO FBC ACC 604.5.1 AND 605.2. A |
| | PULLDOWN GRAB BAR IS NOT COMPLIANT AND SHALL NOT BE |
| | USED. |
| | B. ARCHITECTURAL ISSUE: FBC ACC 604.7 REQUIRES TOILET |
| | PAPER DISPENSER TO BE LOCATED ON THE SIDE WALL 7?-9? |
| | FRONT OF THE WATER CLOSET TO CENTER OF DISPENSER AND |
| | INSIDE THE SPACE OF 15? MINIMUM TO 48? MAXIMUM ABOVE |
| | THE FLOOR. |
| | C. ARCHITECTURAL ISSUE: NOTE THAT PER 604.8.1.2, THE |
| | ENTRY DOOR SHALL BE LOCATED IN THE FRONT PARTITION OR |
| | IN THE SIDE WALL OR PARTITION FARTHEST FROM THE WATER |
| | CLOSET. WHERE LOCATED IN THE FRONT PARTITION, THE DOOR |
| | OPENING SHALL BE 4 INCHES (100 MM) MAXIMUM FROM THE |
| | SIDE WALL OR PARTITION FARTHEST FROM THE WATER CLOSET. |
| | WHERE LOCATED IN THE SIDE WALL OR PARTITION, THE DOOR |
| | OPENING SHALL BE 4 INCHES (100 MM) MAXIMUM FROM THE |
| | FRONT PARTITION. |
| | |
| | 7. NEW COMMENTS |
| | A. PLAN SHEET P-1 AND P-3; MOP SINK LOCATION. RECONCILE |
| | SANITARY ISOMETRIC ON P-3 WITH THE FLOOR PLAN ON P-1. |
| | B. REGARDING THE FOLLOWING ORIGINAL COMMENT: ?TEMPERED |
| | WATER IS REQUIRED AT THE LAVATORIES IN THE TOILET ROOMS |
| | AND BATHROOM PER FBC-PLUMBING. SEC. 416.5. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3.? PER WPB FBC 107.2.1, PROVIDE CUT |
| | SHEET AND SPEC FOR OWNER FURNISHED WALL MOUNTED, ADA |
| | COMPLIANT ANTI-SCALD VALVE SHOWING COMPLIANCE WITH ASSE |
| | 1070 OR CSA B125.3 AS REQUIRED BY FBC PL 416.5 FOR THE |
| | HANDICAPPED LAVATORIES. ALSO PROVIDE A DETAIL OF |
| | INSTALLATION TO SHOW COMPLIANCE WITH FBC ACC 309. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |