| 2019-04-25 10:47:35 | GAS 2ND REVIEW**DENIED** 2ND REQUEST ON ALL COMMENTS**I |
| | WOULD RECOMMEND YOU COMING IN FOR A REVIEW OF YOUR |
| | PLANS BEFORE RE-SUBMITTAL |
| | |
| | **PLEASE NOTE FL ST 553.80 (B)2B WITH RESPECT TO |
| | EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A |
| | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | 1) NOT ADDRESSED. PROVIDE MATERIAL AND PIPE SIZE |
| | LEAVING THE GAS METER THAT YOU ARE CONNECTING |
| | INTO.SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. |
| | G2413.4.1, G2413.4.2. |
| | |
| | 2) NOT ADDRESSED. YOU MUST SHOW ALL APPLIANCES. YOU ARE |
| | MISSING THE WATER HEATER AND THE DRYER. THE PLANS |
| | INDICATE AN EXISTING GAS METER. THE BTU LOAD OF THE |
| | EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU |
| | LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS |
| | PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST |
| | BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A |
| | GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF |
| | EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE |
| | PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN |
| | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO |
| | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| | EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, |
| | 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, |
| | G2413.2, G2413.3. |
| | |
| | 3) NOT ADDRESSED. CITY RECORDS SHOW THIS EXISTING |
| | SYSTEM AS 12" W.C AND NOT 2PSI AS YOU CALL OUT. PLEASE |
| | CLARIFY IS IT YOUR INTEND TO UPGRADE THE GAS METER AND |
| | INSTALL PRESSURE REGS FOR ALL OTHER APPLIANCES? FBC-R G |
| | 2413.2, 2413.4.3 |
| | |
| | 4) PROVIDE A COMPLETE AND ACCURATE GAS ISOMETRIC |
| | DRAWING. FBC 107.3.5 |
| | |
| | 5) YOU SUBMITTED DOCUMENTS CONFLICT WITH EACH OTHER. |
| | ONE SHEET CALL OUT 330,000 BTU'S @ 15' P.E PIPING , THE |
| | NEXT PAGE CALLS OUT 350,000 BTU'S @ 20' P.E. PLEASE |
| | CLARIFY AND REMOVE ALL PAGES THAT ARE NOT PART OF THE |
| | DESIGN. FBC 107.2.1 |
| | |
| | 6) NEW COMMENT: IF 2LB SYSTEM. AT SOME POINT THE SYSTEM |
| | WILL TRANSITION TO SCH 40 METAL PIPING @ .5LB. PROVIDE |
| | ANY AND ALL SIZING TABLES NEEDED TO PROPERLY SIZE THIS |
| | SYSTEM. SUBMIT TWO COPIES OF ALL APPLICABLE SIZING |
| | TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON |
| | THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) |
| | FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN |
| | THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 |
| | FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES |
| | 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. |
| | G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. |
| | |
| | 7) NEW COMMENT: IF 2LB SYSTEM. SHOW THE LOCATION OF ALL |
| | MP (STEP-DOWN) REGULATORS. A LISTED SHUTOFF VALVE SHALL |
| | BE INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR. |
| | 2017 FBC-FUEL GAS SEC.409.4, FBC-RESIDENTIAL SEC. G |
| | 2420.4. |
| | |
| | 8) NEW COMMENT: IF 2LB SYSTEM. SHOW THE DISTANCE FROM |
| | THE 2 PSI REGULATOR TO THE APPLIANCE. COMPLY WITH 2017 |
| | FBC-FUEL GAS SEC. 402.4.1 OR 2017 FBC-RES. SEC. |
| | G2413.4.1, G2413.4.2 FOR THE PROPER PIPE SIZE AND BTU |
| | LOAD. |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |
| | [email protected] |
| | [email protected] |
| | |
| | |