| 2019-03-27 17:30:25 | GAS 1ST REVIEW**DENIED** |
| | |
| | 1) SHOW WHERE YOU ARE CONNECTING INTO THE EXISTING |
| | SYSTEM. PROVIDE PIPE MATERIAL AND SIZE. SUBMIT AN |
| | ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL |
| | CUT SECTIONS OF PIPE PER 2017 FBC-FUEL GAS, SECS. |
| | 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. G2413.4.1, |
| | G2413.4.2. |
| | |
| | 2) CITY RECORDS (PERMIT # 04051271 LIST OTHER GAS |
| | FIXTURES IN HOME. LIST THE BTU LOAD OF EACH APPLIANCE |
| | AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017 |
| | FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4 |
| | AND TABLES G2413.4 (1 ) THROUGH G2413.4 THE PLANS |
| | INDICATE AN EXISTING GAS METER. THE BTU LOAD OF THE |
| | EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU |
| | LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS |
| | PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST |
| | BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A |
| | GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF |
| | EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE |
| | PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN |
| | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO |
| | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| | EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, |
| | 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, |
| | G2413.2, G2413.3. |
| | |
| | 3) CITY RECORDS SHOW THIS SYSTEM AS 12" W.C AND NOT 2 |
| | LB AS YOU CALL OUT. PLEASE CLARIFY. IS IT YOUR INTENT |
| | TO INSTALL PRESSURE REG'S AT ALL FIXTURES? INDICATE THE |
| | DELIVERY PRESSURE (PSI) OF THE SYSTEM ON THE PLAN PER |
| | 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 THRU 402.6 OR 2017 |
| | FBC RES. SEC. G2413.2, G2413.4.3. |
| | |
| | 4) PROVIDE A COMPLETE AND ACCURATE GAS ISOMETRIC |
| | DRAWING. FBC 107.3.5 |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |
| | THUNT@CGA SOLUTIONS.COM |
| | |