Plan Review Notes
Plan Review Notes For Permit 19030784
Permit Number 19030784
Review Stop P
Sequence Number 2
Notes
Date Text
2019-04-30 10:23:30PLUMBING 2ND REVIEW**DENIED**
  
 FL ST 553.80 (B)2B WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS
 IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
  
  
 1) ***ANSWERED WITH NEW COMMENT*I UNDERSTAND THAT
 PRECISION RENOVATIONS IS KNOW TAKING OVER THE ENTIRE
 PROJECT PER THE SIGNED CONTRACT SUBMITTED. A CHANGE OF
 CONTRACTOR FORM IS REQUIRED FOR ALL TRADES.
  
 2) 2ND REQUEST: PROVIDE EXISTING FLOOR PLAN AS PER CITY
 RECORDS UNDER PERMIT # 17030482 AND INSPECTORS PHOTOS
 THERE IS SIGNIFICANT CHANGE TO THE FLOOR PLAN. FBC
 107.3.5. OWNER PURCHASED HOME ON 7/16/18, YOU CONTRACT
 LIST YOUR FIRST SITE VISIT AS 10/1/18. THE FIELD
 INSPECTOR FOUND WORKERS ON-SITE WORKING. ANY AND ALL
 WORK UNPERMITTED WORK IS THE RESPONSIBILITY OF THE
 CURRENT OWNER. PROVIDE AN EXISTING FLOOR PLAN AND A
 PROPOSED FLOOR PLAN.FBC 107.3.5
  
 3) PROVIDE A COMPLETE SANITARY RISER ISOMETRIC SHOWING
 ALL NEW WORK. FBC 107.3.5
 (A) CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND
 DRAWN UPON SUITABLE MATERIAL. RISER ISOMETRIC IS IN
 PENCIL.PENCIL IS NOT PERMITTED. FBC 107.2.1
 (B) CONSTRUCTION DOCUMENTS SHALL BE SIGNED BY THE
 PERSON TAKING RESPONSIBILITY F.S 471, 481, 489
  
 4) PROVIDE SHOWER PAN DETAIL AND PRODUCT BEING USED.
 PROVIDE DRAWING OF PAN SHOWING PRE-PITCH @ 2% AND SHOW
 CURB HEIGHT. FBC 107.2.1
  
 5) 2ND REQUEST:EXPOSE ALL WORK REQUIRING INSPECTION. IT
 SHALL BE THE DUTY OF THE PERMIT APPLICANT TO CAUSE THE
 WORK TO REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES. WPB AMEND TO THE FBC 110.1
 (A)PLEASE PROVIDE A NARRATIVE ON HOW YOU INTENT TO
 EXPOSE ALL COVERED WORK TO ALLOW THE CITY'S INSPECTION
 STAFF TO PROPERLY PERFORM THE REQUIRED INSPECTIONS FBC
 110.1.
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
  