2019-04-08 14:14:41PLUMBING 1ST REVIEW**DENIED**
  
 1) COVER PAGE LIST CODES IN PLACE AS FBC 210 AND 2014.
 AS OF 12/31/2107 WE ARE CURRENTLY USING THE 2017 FBC.
 THIS PROJECT WOULD FALL UNDER THE THE 2017 6TH ED
 EXISTING BUILDING CODES CHAPTERS 7,8,9.
  
 2) BOTH THE EXAM ROOM AND PRETEST SINK SHALL COMPLY
 WITH FBC-A 212.3 AS AT LEAST 1 OF EACH TYPE SHALL BE
 PROVIDED IN EACH ACCESSIBLE ROOM. PROVIDE CLEAR FLOOR
 SPACE, TURNING SPACE, AND COUNTER TOP HEIGHT OF 34" ON
 PLAN. FBC-A 606
  
 3) SHT. P3.0. YOU MUST PROVIDE A AN APPROVED ASSE 1070
 DEVICE FOR TEMPERING HANDSINKS. FBC-P 607.1.2.
 TEMPERING WATER MY MEANS OF THE WATER HEATERS CONTROLS
 IS NOT PERMITTED. FBC-P 607.1.1
  
 4) PROVIDE NOTE ON PLAN THE NEW SINKS SHALL DISCHARGE
 DOWNSTREAM OF THE BATHROOM GROUP WET VENT. FBC 912.1
  