| Plan Review Notes For Permit 19030753 |
| Permit Number |
19030753 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-04-10 15:27:49 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19030753 | | | 4/10/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1.0: REFER TO SECTION 510.1 FBC M AND | | | DESCRIBE THE ACTIVITIES AND PROCESSES THAT TAKE PLACE | | | IN THE LAB AND WHAT MATERIALS OR CHEMICALS ARE USED AND | | | STORED THERE. IF THIS ROOM IS CLASSIFED AS A LAB THEN | | | AN EXHAUST VENTILATION SYSTEM IS REQUIRED, AND | | | RECIRCULATION OF AIR FROM THE ROOM IS PROHIBITED- TABLE | | | 403.3.1.1 FBC M. PLEASE PROVIDE EXPALNATORY NOTES ON | | | THE PLAN TO CLARIY. IF THIS ROOM IS NOT A LAB, PLEASE | | | CHANGE THE NAME. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|