2019-04-22 08:56:52BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ON DRAWING SHEET G1.0 UNDER BUILDING INFO, SPECIFY
 THE USE OF THE 2014 FBC 5TH EDITION. THE CURRENT
 BUILDING CODE IS THE 2017 FBC 6TH EDITION. PLEASE
 VERIFY AND RE-SUBMIT. FBC 107
  
 2. DRAWING SHEET A1.0 UNDER GENERAL FLOOR NOTES, NOTE
 NUMBER 7 INDICATES "CONCRETE USED TO PATCH ANY
 PENETRATION MUST MATH EXISTING ADJACENT SLAB THICKNESS,
 REIFORCEMENT AND TREATED WITH CRETSEAL APPLICATION TO
 PREVENT MOISTURE MIGRATION" HOWEVER NO STRUCTURAL
 DETAIL WAS PROVIDED. PLEASE PROVIDE A STRUCTURAL DETAIL
 WERE SHOWS CONNECTION BETWEEN EXISTING SLAB ON GRADE
 AND THE SPECIFICS FOR THE REPAIR. FBC 107