| Date |
Text |
| 2019-04-03 17:50:55 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SEVERAL DEVICES IN SUBMITTAL PACKET ARE NOT LISTED |
| | IN THE U.S. BY UL OR ANY OTHER NATIONALLY RECOGNIZED |
| | TESTING LABORATORY (NRTL). PROVIDE CUT SHEETS SHOWING |
| | LISTED DEVICES. FBC 107.2.1 NEC 90.7.110.2, 110.3B |
| | |
| | INFORMATIONAL NOTE: CE IS NOT AN ACCEPTED NRTL IN THE |
| | U.S. CE IS A CANADIAN/EUROPEAN LISTING |
| | |
| | 2. ALTRONIX POWER SUPPLY IS TO BE HARD WIRED PER |
| | MANUFACTURES INSTALLATION INSTRUCTIONS. NEC 110.3B |
| | ELECTRICAL PERMIT WILL BE REQUIRED BY LICENSED |
| | ELECTRICIAN FOR ALL 120V CIRCUITS AND CONNECTIONS TO |
| | NEW POWER SUPPLIES. F.S. 489.505 #7 |
| | |
| | 3. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| | 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | 4. SEPARATE LOW VOLTAGE AND ELECTRICAL PERMIT REQUIRED |
| | FOR EACH BUILDING WHERE WORK IS TO BE PERFORMED. ONE |
| | PLAN STATING "TYPICAL" FOR BUIDLINGS 1-20 WILL NOT |
| | SUFFICE. SUBMIT PLANS AND PERMIT APPLICATIONS WITH |
| | PROPER ADDRESSES FOR EACH BUILDING. FBC 107. F.S. 553 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |