Plan Review Notes
Plan Review Notes For Permit 19030681
Permit Number 19030681
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-08 10:15:521) THE NARRATIVE FOR SHT.A-1.5 STATES "ROOF DRAIN
 RELOCATION" BUT I DO NOT SEE ANY ROOF DRAINS ON THE
 PLAN. CLARIFY.
 2) SHT. A-6.5.1 & A-6.5.2 - DETAIL "A" - A 30 INCH BY
 48 INCH CLEAR FLOOR SPACE IS REQUIRED OUTSIDE THE SWING
 OF THE DOOR PER THE FAIR HOUSING DESIGN MANUAL. CLEARLY
 SHOW THIS CLEAR FLOOR SPACE ON THE DETAIL.
 3) SHT. A-9.1 - THERE ARE TWO FIRESTOP DETAILS THAT DO
 NOT SHOW ANY SYSTEM NUMBER AND ONE DOES NOT HAVE ANY F
 RATING ON THE DETAIL. SUBMIT THE REQUIRED INFORMATION.
 WPB AMEND. TO FBC SEC. 107.2.1.
 4) SHT. A-9.2 - SUPPLY THE SYSTEM NUMBER FOR THE 2 HOUR
 FIRESTOP SYSTEM DETAIL. WPB AMEND. TO FBC SEC. 107.2.1.
 5) SHT. A-9.3 - THERE ARE NO SYSTEM NUMBERS ON ANY OF
 THE FIRESTOP DETAILS. SUPPLY ALL THE REQUIRED
 INFORMATION. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  