2019-06-10 14:43:301) SHT. A08.01 - DETAIL B1 - SHOW THE CLEAR FLOOR SPACE
 FOR THE LAVATORY AND THE WATER CLOSET.
 2) SHT. A08.01 - DETAIL C 3 - THE TOILET PAPER
 DISPENSER SHALL BE LOCATED A MINIMUM OF 15 INCHES AND A
 MAXIMUM OF 48 INCHES FROM THE FINISH FLOOR.
 3) SHT. A08.01 - DETAIL D3 - THE GRAB BARS SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT TO THE
 CENTERLINE.
 4) SHT. P01.02 - IDENTIFY ALL OF THE PLUMBING FIXTURES
 ON ALL OF THE WATER PIPING IAOMETRICS. WPB AMEND. TO
 FBC SEC. 107.2.1.
 5) P01.02 - IDENTIFY THE CONTINUATION POINTS OF THE
 WATER LINES FOR EACH PIPING ISOMETRIC EITHER BY ALPHA
 OR NUMERICAL IDENTIFIERS. AS DRAWN, I CANNOT DETERMINE
 WHERE THE CONTINUATION OF THE WATER LINES START OR END.
 WPB AMEND. TO FBC SEC. 107.2.1.
 6) P01.02 - ALTHOUGH IT IS SHOWN AS EXISTING, PLEASE
 SHOW THE TEMPERATURE AND PRESSURE RELIEF LINE FOR THE
 WATER HEATER AND THE LOCATION OF THE TERMINATION POINT
 OF THE RELIEF LINE.
 7) SHT. P02.02 - IDENTIFY THE CONTINUATION POINTS OF
 THE SANITARY LINES FOR EACH PIPING ISOMETRIC BY EITHER
 ALPHA OR NUMERICAL IDENTIFIERS.WPB AMEND. TO FBC SEC.
 107.2.1.
 8) BACKFLOW PREVENTION DEVICES SHALL BE REQUIRED ON
 BEVERAGE DISPENSERS (ASSE 1022), COFFEE MACHINES AND
 NONCARBONATED BEVERAGE DISPENSERS (ASSE 1022) AND ON
 ANY ICEMAKER.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW