| 2019-06-05 15:10:54 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19030673 |
| | 6/5/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) COMMISSIONING OF THE MECHANICAL AND ELECTRICAL |
| | LIGHTING SYSTEMS IS REQUIRED PER SECTION C408.1 FBC-17 |
| | ENERGY CONSERVATION. SUBMIT A COMMISSIONING PLAN AS |
| | OUTLINED IN SECTION C408.2.1 AND DESCRIBED IN SECTIONS |
| | C403.2.2- C408.2.3.3. PLEASE NOTE THAT A COPY OF THE |
| | COMMISSIONING REPORT SHALL BE SUBMITTED FOR REVIEW AT |
| | FINAL INSPECTION. |
| | |
| | 2) A SEPARATE PERMIT IS REQUIRED FOR THE REFRIGERATRION |
| | WORK- SECTION 107.2.1 WPB. PLEASE REMOVE THE |
| | REFRIGERATIONS PLANS FROM THE SETS AND RESUBMIT UNDER A |
| | SEPARATE PERMIT. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |