| 2019-06-12 12:47:31 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SHEET E01.01, PLAN STATES THAT PUBLIX IS SUPPLYING |
| | THE LIGHT FIXTURES. IN REFERENCE TO VALUE OF THE STATED |
| | WORK, ALL MATERIALS AND LABOR SHOULD BE INCLUDED IN THE |
| | STATED VALUE. UNDER THIS PERMIT, THE VALUES FOR |
| | BUILDING, MECHANICAL, ELECTRICAL, AND PLUMBING SHOULD |
| | BE INCLUDED. REMOVE ANY VALUES FOR SYSTEMS THAT REQUIRE |
| | A SEPARATE PERMIT, AS THOSE VALUES WILL BE REQUIRED |
| | WHEN PERMIT APPLICATION IS MADE FOR THOSE SEPARATE |
| | PERMITS. SEE NOTE 2 BELOW. PROVIDE COPY OF SIGNED |
| | CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL |
| | MATERIALS AND LABOR. THIS IS FOR TOTAL PROJECT, NOT |
| | JUST ELECTRICAL. WPB FBC 109.3 |
| | 2. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC |
| | 105.1, 107.2.1 |
| | 3. LOAD CALCULATION DOES NOT DETAIL THE ADDITIONAL |
| | LOAD, AND THE MATH APPEARS TO BE INCORRECT. IS THE NEW |
| | LOAD DECREASING BY 109 KVA? THE LOAD CALC SHOWS 481 - |
| | 109 EQUALS 559. THIS MATH IS NOT WORKING. THE LOAD |
| | CALCULATION SHOULD INCLUDE THE EXISTING DEMAND, AND |
| | ADDITIONAL 25% OF THE EXISTING DEMAND, PLUS THE |
| | PROPOSED NEW LOAD TO COMPLY WITH NEC 220.87. |
| | ADDITIONALLY, PROVIDE PROOF OF STATED FPL LOAD FOR ONE |
| | YEAR. PROVIDE CORRECTION. NEC 220.87 |
| | 4. DEMAND FACTOR APPLIED TO PANEL K IS NOT PER CODE. |
| | THERE ARE ONLY 5 PIECES OF EQUIPMENT SHOWN IN THE PANEL |
| | SCHEDULE. THEREFORE, THE DEMAND FACTOR SHOULD BE 70%. |
| | PROVIDE CORRECTION. NEC 220.56 |
| | 5. POWER PLAN SHEET E02.01 DOES NOT SHOW DARKENED LINES |
| | ON THE NEW REFRIGERATED/FROZEN CASES THAT ARE SHOWN AS |
| | NEW ON SHEET EQ01.01. PROVIDE CLARIFICATION/CORRECTIONS |
| | AS NEEDED. WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |