Plan Review Notes
Plan Review Notes For Permit 19030673
Permit Number 19030673
Review Stop E
Sequence Number 1
Notes
Date Text
2019-06-12 12:47:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E01.01, PLAN STATES THAT PUBLIX IS SUPPLYING
 THE LIGHT FIXTURES. IN REFERENCE TO VALUE OF THE STATED
 WORK, ALL MATERIALS AND LABOR SHOULD BE INCLUDED IN THE
 STATED VALUE. UNDER THIS PERMIT, THE VALUES FOR
 BUILDING, MECHANICAL, ELECTRICAL, AND PLUMBING SHOULD
 BE INCLUDED. REMOVE ANY VALUES FOR SYSTEMS THAT REQUIRE
 A SEPARATE PERMIT, AS THOSE VALUES WILL BE REQUIRED
 WHEN PERMIT APPLICATION IS MADE FOR THOSE SEPARATE
 PERMITS. SEE NOTE 2 BELOW. PROVIDE COPY OF SIGNED
 CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL
 MATERIALS AND LABOR. THIS IS FOR TOTAL PROJECT, NOT
 JUST ELECTRICAL. WPB FBC 109.3
 2. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 3. LOAD CALCULATION DOES NOT DETAIL THE ADDITIONAL
 LOAD, AND THE MATH APPEARS TO BE INCORRECT. IS THE NEW
 LOAD DECREASING BY 109 KVA? THE LOAD CALC SHOWS 481 -
 109 EQUALS 559. THIS MATH IS NOT WORKING. THE LOAD
 CALCULATION SHOULD INCLUDE THE EXISTING DEMAND, AND
 ADDITIONAL 25% OF THE EXISTING DEMAND, PLUS THE
 PROPOSED NEW LOAD TO COMPLY WITH NEC 220.87.
 ADDITIONALLY, PROVIDE PROOF OF STATED FPL LOAD FOR ONE
 YEAR. PROVIDE CORRECTION. NEC 220.87
 4. DEMAND FACTOR APPLIED TO PANEL K IS NOT PER CODE.
 THERE ARE ONLY 5 PIECES OF EQUIPMENT SHOWN IN THE PANEL
 SCHEDULE. THEREFORE, THE DEMAND FACTOR SHOULD BE 70%.
 PROVIDE CORRECTION. NEC 220.56
 5. POWER PLAN SHEET E02.01 DOES NOT SHOW DARKENED LINES
 ON THE NEW REFRIGERATED/FROZEN CASES THAT ARE SHOWN AS
 NEW ON SHEET EQ01.01. PROVIDE CLARIFICATION/CORRECTIONS
 AS NEEDED. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved