| Plan Review Notes For Permit 19030580 |
| Permit Number |
19030580 |
|
| Review Stop |
SIGNATURE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-04-18 05:50:30 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | COMMENT FROM FIRST REVIEW: | | | | | | 1. CIVIL PAGES ARE DIGITALLY SIGNED BY BRITT L. | | | STEPHENS. SEE FS471, FAC61G15-23.002; A SEAL AND | | | PRINTED LICENSE NUMBER IS REQUIRED. AN IMAGE OF A SEAL | | | IS ACCEPTABLE TO SATISFY BOTH REQUIREMENTS. | | | | | | SECOND REVIEW: | | | | | | IT IS NOT CLEAR IF THE COMMENT WAS PROPERLY CONVEYED TO | | | THE ENGINEER AS THE REPONSE NARRATIVE STATES THAT THIS | | | IS COMMENT #2 FOR ENGINEERING. IT IS ALSO NOT CLEAR IF | | | THE ENGINEER DISAGREES WITH THE COMMENT AS THE RESPONSE | | | STATES "PLEASE SEE THE ATTACHED PLANS WITH REQUESTED | | | SEAL." OF THE 13 PAGES SIGNED BY THE ENGINEER, ONLY TWO | | | NEW PAGES WERE UPLOADED, ALL PAGES ARE DIGITALLY SIGNED | | | BUT LACK A SEAL. | | | | | | PLEASE SEE FAC61G15-23.004 FOR LANGUAGE REQUIRED TO BE | | | INCLUDED IN THE DIGITAL SIGNATURE. | | | | | | AS DISCUSSED WITH BILL DUFFY AND DAVID PELLEGRI, THIS | | | ISSUE WILL NOT DELAY ISSUANCE OF THIS PERMIT, BUT | | | ENGINEER IS TO COMPLY IN THE FUTURE. | | | | | | |
|