Plan Review Notes
Plan Review Notes For Permit 19030570
Permit Number 19030570
Review Stop B
Sequence Number 1
Notes
Date Text
2019-03-13 07:27:12PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 CORRECTIONS:
  
 1. PROVIDE A SKETCH/LAYOUT SHEET SHOWING THE LOCATION
 OF ALL SHUTTERS TO BE INSTALLED.THIS LAYOUT SHEET
 SHOULD INDICATE WINDOW/DOOR OPENINGS NUMBERED TO MATCH
 WITH THE SCHEDULE FOR INSTALLATION OF OPENING
 PROTECTIVE DEVICES.
  
  
 2. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET):
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
  
 3. WHEN COMPLETING THE INSTALLATION SCHEDULE FACTORS
 APPLY DEPENDING ON SUBSTRATE, EDGE DISTANCE AND
 FASTENER. FOR FASTENER, IF USING TAPCON, BE SPECIFIC AS
 TO WHICH TAPCON.
  
 PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  
 4. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC
 R 310.4; INCLUDE ROOM DESIGNATION.