| Plan Review Notes For Permit 19030570 |
| Permit Number |
19030570 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-03-13 07:27:12 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | CORRECTIONS: | | | | | | 1. PROVIDE A SKETCH/LAYOUT SHEET SHOWING THE LOCATION | | | OF ALL SHUTTERS TO BE INSTALLED.THIS LAYOUT SHEET | | | SHOULD INDICATE WINDOW/DOOR OPENINGS NUMBERED TO MATCH | | | WITH THE SCHEDULE FOR INSTALLATION OF OPENING | | | PROTECTIVE DEVICES. | | | | | | | | | 2. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION | | | OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL | | | INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL | | | SPREADSHEET): | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS?PAGE=2 | | | | | | 3. WHEN COMPLETING THE INSTALLATION SCHEDULE FACTORS | | | APPLY DEPENDING ON SUBSTRATE, EDGE DISTANCE AND | | | FASTENER. FOR FASTENER, IF USING TAPCON, BE SPECIFIC AS | | | TO WHICH TAPCON. | | | | | | PLEASE CONTACT ME IF YOU NEED ASSISTANCE. | | | | | | 4. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC | | | R 310.4; INCLUDE ROOM DESIGNATION. |
|