2019-06-20 14:48:42ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SWITCHES ARE NOT ALLOWED IN SHOWER AREAS. SEE MASTER
 BATH SHOWER
  
 SWITCHES
  
 A SURFACE MOUNTED SWITCH OR CIRCUIT BREAKER LOCATED IN
 A DAMP OR WET LOCATION OR OUTSIDE OF A BUILDING SHALL
 BE ENCLOSED IN A WEATHERPROOF ENCLOSURE OR CABINET. A
 FLUSH-MOUNTED SWITCH OR CIRCUIT BREAKER IN A DAMP OR
 WET LOCATION SHALL BE EQUIPPED WITH A WEATHERPROOF
 COVER. SWITCHES SHALL NOT BE INSTALLED WITHIN WET
 LOCATIONS IN TUB OR SHOWER SPACES UNLESS INSTALLED AS
 PART OF A LISTED TUB OR SHOWER ASSEMBLY. [404.8(A),
 (B), AND (C)].
  
 2. RECESSED LIGHT IN SHOWER AREA NEEDS TO BE VAPOR
 PROOF.
  
 E4003.9WET OR DAMP LOCATIONS.
 LUMINAIRES INSTALLED IN WET OR DAMP LOCATIONS SHALL BE
 INSTALLED SO THAT WATER CANNOT ENTER OR ACCUMULATE IN
 WIRING COMPARTMENTS, LAMP HOLDERS OR OTHER ELECTRICAL
 PARTS. ALL LUMINAIRES INSTALLED IN WET LOCATIONS SHALL
 BE MARKED SUITABLE FOR WET LOCATIONS. ALL LUMINAIRES
 INSTALLED IN DAMP LOCATIONS SHALL BE MARKED SUITABLE
 FOR WET LOCATIONS OR SUITABLE FOR DAMP LOCATIONS.
 (410.10)
  
  
  
  
  
  
  