| 2019-06-20 14:48:42 | ELECTRICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 3RD REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. SWITCHES ARE NOT ALLOWED IN SHOWER AREAS. SEE MASTER |
| | BATH SHOWER |
| | |
| | SWITCHES |
| | |
| | A SURFACE MOUNTED SWITCH OR CIRCUIT BREAKER LOCATED IN |
| | A DAMP OR WET LOCATION OR OUTSIDE OF A BUILDING SHALL |
| | BE ENCLOSED IN A WEATHERPROOF ENCLOSURE OR CABINET. A |
| | FLUSH-MOUNTED SWITCH OR CIRCUIT BREAKER IN A DAMP OR |
| | WET LOCATION SHALL BE EQUIPPED WITH A WEATHERPROOF |
| | COVER. SWITCHES SHALL NOT BE INSTALLED WITHIN WET |
| | LOCATIONS IN TUB OR SHOWER SPACES UNLESS INSTALLED AS |
| | PART OF A LISTED TUB OR SHOWER ASSEMBLY. [404.8(A), |
| | (B), AND (C)]. |
| | |
| | 2. RECESSED LIGHT IN SHOWER AREA NEEDS TO BE VAPOR |
| | PROOF. |
| | |
| | E4003.9WET OR DAMP LOCATIONS. |
| | LUMINAIRES INSTALLED IN WET OR DAMP LOCATIONS SHALL BE |
| | INSTALLED SO THAT WATER CANNOT ENTER OR ACCUMULATE IN |
| | WIRING COMPARTMENTS, LAMP HOLDERS OR OTHER ELECTRICAL |
| | PARTS. ALL LUMINAIRES INSTALLED IN WET LOCATIONS SHALL |
| | BE MARKED SUITABLE FOR WET LOCATIONS. ALL LUMINAIRES |
| | INSTALLED IN DAMP LOCATIONS SHALL BE MARKED SUITABLE |
| | FOR WET LOCATIONS OR SUITABLE FOR DAMP LOCATIONS. |
| | (410.10) |
| | |
| | |
| | |
| | |
| | |
| | |
| | |