Plan Review Notes
Plan Review Notes For Permit 19030555
Permit Number 19030555
Review Stop P
Sequence Number 2
Notes
Date Text
2019-05-24 15:23:44PLUMBING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. IDENTIFY SIZE OF KITCHEN DRAIN ON ISO.
 2. DISH WASHER NOT SHOWN ON ISO.
 3. WASHING MACHINE NOT SHOWN ON ISO.
 4. TWO FIXTURES LOCATED DOWNSTREAM OF WET VENT ON
 BATHROOM GROUP NOT PERMITTED.
 5. BATHROOM ISO SHOWS SHOWER, PLAN SHOWS TUB.
 6. M-BATH SHOWER COMPARTMENT IS LABELED AS A LINEN
 CLOSET. - PG. EP1.
 7. KITCHEN ISO SHOWS A SINGLE SINK. PLAN SHOWS A DOUBLE
 SINK.
  
 ADDRESS THE ABOVE COMMENTS AND RE-SUBMIT.
  
  