| 2019-05-24 15:14:48 | ELECTRICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. VALUE APPEARS LOW FOR PROPOSED SCOPE OF WORK. |
| | CITY OF WPB CHPT. 1 ? VALUE |
| | 109.3 BUILDING PERMIT VALUATIONS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE |
| | OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT |
| | RENTAL TO VERIFY VALUE. |
| | |
| | 2. WP GFI OUTLET REQUIRED AT FRONT OF HOUSE. |
| | FOR A ONE FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY |
| | DWELLING THAT IS AT GRADE LEVEL, AT LEAST ONE |
| | RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND NOT |
| | MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| | PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7 |
| | |
| | 3. IDENTIFY LOCATION OF SERVICE ON PLAN. |
| | ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS PERMITTED. |
| | PROVIDE DETAILS OF SERVICE FOR MAIN HOUSE. PROVIDE |
| | CORRECTION AND/OR CLARIFICATION. FBC 107.2.1; NEC |
| | 230.2; FBC RE E3601.2 |
| | |
| | 4. KITCHEN SINK COUNTER OUTLET SPACING NOT PER CODE. |
| | PROVIDE CORRECTION. NEC 210.52(C)(1); FBC RE E3901.4 |
| | |
| | |
| | |
| | |
| | |
| | |