| 2019-03-26 13:03:46 | ELECTRICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. IS SERVICE EXISTING OR AN UPGRADE? FBC E 808.1 NEW |
| | INSTALLATIONS. ALL NEWLY INSTALLED ELECTRICAL EQUIPMENT |
| | AND WIRING RELATING TO WORK DONE IN ANY WORK AREA SHALL |
| | COMPLY WITH ALL APPLICABLE REQUIREMENTS OF NFPA 70 |
| | EXCEPT AS PROVIDED FOR IN SECTION 808.3. |
| | 2. PROVIDE FLOOR PLAN. IDENTIFY LOCATION OF ALL WORK. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 3. IDENTIFY WHICH BATHROOM THE PROPOSED NEW 20 AMP |
| | CIRCUT WILL BE INSTALLED. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 4. DISHWASHER OUTLET SHALL BE GFCI PROTECTED. . PROVIDE |
| | GFCI PROTECTION FOR DISHWASHERS. NEC 210.8(D); FBC RE |
| | E3902.10. |
| | 5. KITCHEN COUNTER CONFIGURATION IS DIFFERENT THAN |
| | COUNTER LAYOUT ON SUBMITTED FLOOR PLAN. CANNOT VERIFY |
| | OUTLET SPACING. E3901.4 COUNTERTOP RECEPTACLES. IN |
| | KITCHENS PANTRIES, BREAKFAST ROOMS, DINING ROOMS AND |
| | SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE OUTLETS FOR |
| | COUNTERTOP SPACES SHALL BE INSTALLED IN ACCORDANCE WITH |
| | SECTIONS E3901.4.1 THROUGH E3901.4.5. |
| | 6. SMOKE DETECTOR REQUIRED IN BEDROOM # 3. FBC- |
| | 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO FBC-R |
| | 314.3.1 AS REQUIRED FOR NEW DWELLINGS. |
| | 7. GAS FIRED APPLIANCE WITHIN DWELLING UNIT. PROVIDE |
| | C/O DETECTOR. FBC-R 315.1 ? PROVIDE CARBON MONOXIDE |
| | ALARMS WITHIN 10 FEET OF EACH SLEEPING ROOM. |
| | 8. AFCI PROTECTION REQUIRED FOR NEW OUTLETS. . BRANCH |
| | CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, |
| | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. PROVIDE COMPLIANCE. NEC |
| | 210.12; FBC RE E3902.16. |
| | 9. CONTRACTOR TO PRINT NAME AND SIGN PLAN. FBC 107.2.1 |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5) AND F.S. 481.229. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |
| | |