| 2019-03-26 09:04:42 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. RISER DIAGRAM SHOWS 2/0 ALUMINUM CONDUCTORS FOR THE |
| | FEED TO THE INTERIOR PANEL WITH A 1/0 ALUMINUM GROUNDED |
| | CONDUCTOR AND A # 6 COPPER EQUIPMENT GROUNDING |
| | CONDUCOTR. ALUMINUM CONDUCTORS OF THIS SIZE ARE NOT |
| | RATED FOR A 200 AMP SERVICE. ADDITIONALLY, IF YOU WANT |
| | TO INSTALL A REDUCED GROUNDED CONDUCTOR SIZE, A LOAD |
| | CALCULATION FOR THE GROUNDED CONDUCTOR IS REQUIRED. |
| | PROVIDE CORRECTIONS. FBC RE E3603.1 |
| | 2. THERE IS A CONFLICT ON THE PLAN IF REFERENCE TO AFCI |
| | PROTECTION REQUIRED. THERE IS ONE NOTE TO THE RIGHT OF |
| | FLOOR PLANS THAT ACCURATELY STATES THE REQUIREMENT. |
| | HOWEVER, THERE IS ANOTHER NOTE BELOW THE RISER DIAGRAM |
| | THAT INCORRECTLY STATES THE REQUIREMENT. REMOVE OR EDIT |
| | THE NOTE BELOW THE RISER DIAGRAM. WPB FBC 107.2.1 |
| | 3. RISER DIAGRAM SHOWS THE 2011 NEC AS BASIS FOR THE |
| | REQUIREMENT OF NEC 250.94. THIS IS NOT THE CURRENT |
| | CODE, PROVIDE CORRECTION. WPB FBC 107.2.1; FBC PREFACE |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |