2019-04-02 17:30:23***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC ER = FBC ENERGY RESIDENTIAL
 FBC BRS = FBC BUILDING REFERENCED STANDARDS (AWS =
 AMERICAN WELDING SOCIETY)
  
 BUILDING REVIEW DENIED:
  
 1. FBC B 107.2.1 THE FOUNDATION/FOOTING DETAILS ARE NOT
 COMPLETE:
 A. FOOTING DIMENSIONS ARE NOT COMPLETE
 B. FOOTING REINFORCEMENT IS NOT COMPLETE
 C. EMBEDDED STEEL PLATES WITH 12" LONG DOWEL DETAILS
 ARE NOT COMPLETE (MISSING TYPE OF STEEL, DIAMETER, &
 WELDING SPECS)
 PROVISO: IN ADDITION TO THE REQUIREMENTS ABOVE,BEARING
 CAPACITY/SOIL COMPACTION TEST RESULTS/TERMITE
 TREATMENT/FORM BOARD SURVEY CAN BE ON-SITE AT TIME OF
 INSPECTION.
  
 2. FBC B 107.2.1 THE HANDRAIL TO MAIN STRUCTURE
 CONNECTIONS ARE NOT CLEAR.
  
 3. FBC R 310.2.1 THE 1ST FLOOR BEDROOM WINDOW SIZE
 (CLEAR OPENING IS TOO SMALL).
  
 4. FBC B 107.2.1 & FBC R 903.2 THE LOW ROOF AT SIDE
 ENTRY IS MISSING DETAILS FOR THE STRUCTURAL CONNECTIONS
 TO THE BUILDING AND ROOF FLASHING.
  
 5. FBC B 310 ACCORDING TO THE PLAN DETAILS THE
 OCCUPANCY CLASSIFICATION SHOULD BE "R-3".
  
 6. FBC ER 401.2 ENERGY CALCULATIONS FOR THE STRUCTURE
 ARE REQUIRED.
 PROVISO: IN ADDITION TO REQUIREMENTS ABOVE, BUILDING
 THERMAL ENVELOPE TESTING WILL BE REQUIRED PRIOR TO
 FINAL INSPECTION.
  
 7. FBC B 107.2.1 & FBC R 316.3 THE PRODUCT APPROVALS
 FOR ICENYNE INSULATION (INCLUDING FLAME SPREAD TEST
 RESULTS) ARE REQUIRED.
  
 8. FBC R 903.2, FBC R 903.4, & FBC R 904.2 THE PLANS
 NEED TO SHOW WOOD DECKING AS A ROOF SUBSTRATE TO MATCH
 THE SUBMITTED N.O.A. 17-0824.09 FOR POLY-GLASS MODIFIED
 BITUMEN ROOF SYSTEM OVER WOOD DECKS AND INDICATE WHICH
 SYSTEM FROM WITHIN THE N.O.A. WILL BE USED.
  
 9. FBC B 107.2.1 & FBC BRS = AWS D1.1 THE PLANS
 INDICATE SEVERAL AREAS WHERE WELDING IS REQUIRED, BUT
 HAVE MINIMAL DETAILS AT: FOOTING BASE PLATES, COLUMN
 CONNECTIONS, WINDOW FRAMING, & JOINING OF CONTAINERS.
 PROVIDE MORE DETAILED INFORMATION ON PLANS.
 PROVISO: IN ADDITION TO THE REQUIREMENTS ABOVE, AWS
 D1.1 CLAUSE 3.1 (WELD PROCEDURE SPECIFICATION/SHOWS
 ESSENTIAL VARIABLES) & CLAUSE 4.2.2 (WELD PERFORMANCE
 QUALIFICATION RECORD/SHOWS WELDERS CERTS) ARE REQUIRED
 AT TIME OF INSPECTION.
  
 10. FBC B 107.2 PROVIDE ENGINEER OF RECORD SIGNED AND
 SEALED LETTER APPROVING THE EXISTING CONDITION FOR THE
 1ST, 2ND, AND ROOF LEVEL STRUCTURAL DECKS.
  
 11. FBC B 107.2.1.3 PROVIDE ENGINEER OF RECORD ANALYSIS
 & CALCULATIONS APPROVING ALL LOADS, AND CONFIGURATIONS
 OF CONTAINERS.
  
 12. PLEASE PROVIDE A BREAK DOWN OF VALUATION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  