| Date |
Text |
| 2019-04-03 13:03:41 | COMMENTS DO NOT APPLY. ALL DOCUMENTS IN PACKAGE AND |
| | APPROVED. T LARGE. |
| 2019-03-22 08:36:32 | GAS 1ST REVIEW**DENIED** |
| | |
| | THERE ARE NO GAS DOCUMENTS/ PLANS SUBMITTED OTHER THEN |
| | A NOTE THAT THE EXISTING SYSTEM MAY NEED TO HAVE THE |
| | PRESSURE CHANGED TO 2P.S.I. |
| | |
| | 1) SUBMIT A PLAN WITH A SYSTEM PROPERLY SIZED STATING |
| | THE REQUIRED PRESSURE NEEDED FOR THE ENTIRE TO WORK |
| | UNDER FULL DEMAND. FBC 107.3.5 |
| | |
| | 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. |
| | G2413.4.1, G2413.4.2. |
| | |
| | 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| | |
| | 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS |
| | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) |
| | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES |
| | G2413.4 (1 ) THROUGH G2413.4 (21. |
| | |
| | 5) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| | G2413.1, G2413.2, & G2413.3 |
| | |
| | 6) ) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. |
| | G2421.1. IF SYSTEM IS 2 LB. |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER |
| | BUILDING DIVISION |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |
| | [email protected] |
| | |
| | |
| | |