| Plan Review Notes For Permit 19030507 |
| Permit Number |
19030507 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-08-06 13:15:36 | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M.1: AHU-1 CANNOT BE HOUSED INSIDE THE | | | HYBERBARIC ROOM. REFER TO SECTION 14.2.1.1.7 NFPA 99: | | | ROOMS HOUSING CLASS OR CLASS B CHAMBERS SHALL BE FOR | | | THE EXCLUSIVE USE OF THE HYPERBARIC OPERATION. AHU-1 | | | MAY REMAIN AND SERVICE THE HYBERBARIC ROOM EXCLUSIVELY | | | BUT THE CURRENT PLAN INDICATES THE UNIT IS SEVICING | | | OTHER ROOMS. | | | | | | CHRIS MONTELLO | | | 561-805-6733 | | | | | | | | | |
|