| 2019-06-27 09:21:25 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19030507 |
| | 6/27/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M.1: AHU-1 CANNOT BE HOUSED INSIDE THE |
| | HYBERBARIC ROOM. REFER TO SECTION 14.2.1.1.7 NFPA 99: |
| | ROOMS HOUSING CLASS OR CLASS B CHAMBERS SHALL BE FOR |
| | THE EXCLUSIVE USE OF THE HYPERBARIC OPERATION. AHU-1 |
| | MAY REMAIN AND SERVICE THE HYBERBARIC ROOM EXCLUSIVELY |
| | BUT THE CURRENT PLAN INDICATES THE UNIT IS SEVICING |
| | OTHER ROOMS. |
| | |
| | 2) M.1:THE FIRE DAMPER IN THE 10X8 OXYGEN ROOM EXHAUST |
| | DUCT IS PROHIBITED PER SECTION 510.7 FBC M. IN |
| | ACCORDANCE WITH SECTION 510.7.3, THE EXHAUST DUCT SHALL |
| | BE ENCLOSED IN FIRE-RATED CONSTRUCTION FROM THE POINT |
| | OF PENETRATION OF THE WALL TO THE OUTLET TERMINAL. THE |
| | DUCT SHALL BE ENCLOSED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING REQUIREMENTS FOR SHAFT |
| | CONSTRUCTION AND SUCH ENCLOSURE SHALL HAVE A MINIMUM |
| | FIRE-RESISTANCE RATING OF NOT LESS THAN THE HIGHEST |
| | FIRE-RESISTANCE-RATED WALL ASSEMBLY PENETRATED. PLEASE |
| | SEE SECTION 510.9 FOR ALLOWABLE DUCT MATERALS- THE |
| | CURRENT SPECIFICATION IS NON-COMPLIANT. PLEASE NOTE |
| | THAT A 2-HR FIRE-RATED HAZARDOUS EXHAUST DUCT WRAP IS |
| | AN ACCEPTABLE ALTERNATIVE TO A CONSTRUCTED FIRE-RATED |
| | SHAFT ENCLOSURE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |