| Plan Review Notes For Permit 19030507 |
| Permit Number |
19030507 |
|
| Review Stop |
MEDGAS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-04-15 11:18:56 | 1ST REVIEW: 19030507 | | | | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | MED GAS COMMENTS: | | | | | | 1. NOTE ON THE PLAN THE MED GAS CONTRACTOR AND THE | | | INSTALLERS SHALL PROVIDE PROFF OF COMPLIANCE WITH FAC | | | 61G4-15.031(1)(4)(A)(B) | | | | | | 2. PROVIDE A DETAIL FOR RESTRAINTS ON THE OXYGEN TANK | | | INCLUDING WALL ANCHORAGE. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. PROVIDE PIPING DETAIL FOR ALL CONNECTION OF THE MED | | | GAS SYSTEM. PER WPB AMEND TO FBC 107.2.1 | | | | | | 4. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTILLATION | | | GUIDES FOR ALL MED GAS EQUIPMENT. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|