2019-04-15 11:18:561ST REVIEW: 19030507
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 MED GAS COMMENTS:
  
 1. NOTE ON THE PLAN THE MED GAS CONTRACTOR AND THE
 INSTALLERS SHALL PROVIDE PROFF OF COMPLIANCE WITH FAC
 61G4-15.031(1)(4)(A)(B)
  
 2. PROVIDE A DETAIL FOR RESTRAINTS ON THE OXYGEN TANK
 INCLUDING WALL ANCHORAGE. PER WPB AMEND TO FBC 107.2.1
  
 3. PROVIDE PIPING DETAIL FOR ALL CONNECTION OF THE MED
 GAS SYSTEM. PER WPB AMEND TO FBC 107.2.1
  
 4. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTILLATION
 GUIDES FOR ALL MED GAS EQUIPMENT. PER WPB AMEND TO FBC
 107.2.1
  