| Date |
Text |
| 2019-04-18 14:37:19 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19030507 |
| | 4/18/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017FBC |
| | FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | NFPA 99- 2015 HEALTH CARE FACILITIES CODE |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET T.1: REFER TO SECTION 425.1 FBC B- ADD THE |
| | NFPA 99-2015 TO THE LIST OF APPLICABLE CODES LISTED |
| | UNDER PROJECT DATA. |
| | |
| | 2) T.1: REFER TO SECTION 14.1.2.1 NFPA-99- PROVIDE THE |
| | CLASSIFICATION OF THE CHAMBER ON THE PLANS- CLASS A- |
| | HUMAN MULTIPLE OCCUPANCY. |
| | |
| | 3) T.1: REFER TO SECTION 14.2.1.2 NFPA 99- A |
| | HYDAULICALLY CALCULATED AUTOMATIC WET PIPE SPRINKLER |
| | SYSTEM MEETING THE REQUIRMENTS OF NFPA 13 OR A WATER |
| | MIST SYSTEM PER NFPA 70 IS REQUIRED FOR THE HYPERBARIC |
| | AND OXYGEN ROOMS. |
| | |
| | 4) P.3: REFER TO SECTIONS 14.2.1.4- 14.2.1.5 NFPA 99- |
| | VERIFY THE MEDICAL OXYGEN SYSTEM MEETS ALL THE |
| | REQUIREMENTS FOR PIPING AND STORAGE OF THE OXYGEN. |
| | |
| | 5) M.1: A FIRE DAMPER IS REQUIRED FOR THE WALL DIFFUSER |
| | PENETRATING THE FIRE-RATED OYXGEN ROOM WALL- SECTION |
| | 607.5.2 FBC M. |
| | |
| | 6) LS.1, M.1, P.3: REFER TO TABLE 307.1(1) FBC B- THE |
| | OXYGEN ROOM IS CLASSIFIED AS AN H-3 OCCUPANCY BASED ON |
| | THE 20, 048 CU. FT. OF OXYGEN BEING STORED IN THE ROOM. |
| | PLEASE SEE SECTION 510.1 FBC M. AND PROVIDE A HAZARDOUS |
| | EXHAUST SYSTEM FOR THE ROOM. SHOW THE EXHAUST DUCT RUN, |
| | TYPE OF DUCT TO BE USED, AND TERMINATION LOCATION- SEE |
| | SECTIONS 510.4, 510.6.5, 510.6.7, 510.7, AND 510.9 FBC |
| | M. A) PROVIDE A ROOF PLAN SHOWING THE LOCATION OF THE |
| | FAN AND CLEARANCE DISTANCES IN ACCORDANCE WITH SECTION |
| | 501.3.1 FBC M, AND IN ACCORDANCE WITH SECTION 304.11- |
| | MINIMUM 10' TO ROOF EDGE OR PROVIDE A GUARD. A) REFER |
| | TO SECTION 9.3.6.5.3 FOR MECHANICAL VENTILATION RATE, |
| | LOCATION OF EXHAUST INLETS, AND REQUIRED CONTINOUS |
| | OPERATION- REMOVE THE THERMOSTAT FROM THE PLAN. B) |
| | PROVIDE A FL. PRODUICT APPROVAL AND/OR MIAMI-DADE NOA |
| | FOR THE MAKEUP AIR LOUVER IN THE OXYGEN ROOM- SECTION |
| | 9N-03 FAC. THE LOUVER SHALL BE AMCA 550 RATED )401.5 |
| | FBC M), AND MAY REQUIRED A FIRE DAMPER IF IT IS |
| | DETERMINED THE EXTERIOR WALL HAS TO BE FIRE-RATED. |
| | |
| | 7) LS.1: THE WALLS ENCLOSING THE OXYGEN ROOM MUST BE |
| | 3-HR FIRE-RESISTANT IN ACCORDANCE WITH TABLE 508.4 FBC |
| | B. |
| | |
| | 8) M.1: PROVIDE EQUIPMENT SCHEDULES FOR THE NEW AC |
| | SYSTEMS, AND SHOW THE LOCATIONS OF THE NEW CONDENSERS- |
| | TABLE C403.2.3(1) AND SECTION C501.7 FBC EC, AND |
| | SECTION 107.2.1 WPB. |
| | |
| | 9) M.1: PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION |
| | OF THE CONDENSERS AND ROOF FANS- SECION 301.15 FBC M. |
| | |
| | 10) M.1: PROVIDE CONDENSATE DISPOSAL PLANS FOR THE NEW |
| | SYSTEMS- SECTION 307.2.1 FBC M. |
| | |
| | 11) M.1, P.3: SUBMIT PRODUCT DATA SHEETS FOR THE |
| | HYPERBARIC CHAMBERS- SECTION 304.1 FBC M. |
| | |
| | 12) M.1, P.3: REFER TO SECTION 5.1.3.1.1 & 5.1.3.1.2- |
| | PROVIDE PRODUCT SPECIFICATION SHEETS FOR THE OXYGEN |
| | TANKS AND CYLINDERS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |