Plan Review Notes
Plan Review Notes For Permit 19030507
Permit Number 19030507
Review Stop M
Sequence Number 1
Notes
Date Text
2019-04-18 14:37:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19030507
 4/18/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017FBC
 FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 NFPA 99- 2015 HEALTH CARE FACILITIES CODE
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET T.1: REFER TO SECTION 425.1 FBC B- ADD THE
 NFPA 99-2015 TO THE LIST OF APPLICABLE CODES LISTED
 UNDER PROJECT DATA.
  
 2) T.1: REFER TO SECTION 14.1.2.1 NFPA-99- PROVIDE THE
 CLASSIFICATION OF THE CHAMBER ON THE PLANS- CLASS A-
 HUMAN MULTIPLE OCCUPANCY.
  
 3) T.1: REFER TO SECTION 14.2.1.2 NFPA 99- A
 HYDAULICALLY CALCULATED AUTOMATIC WET PIPE SPRINKLER
 SYSTEM MEETING THE REQUIRMENTS OF NFPA 13 OR A WATER
 MIST SYSTEM PER NFPA 70 IS REQUIRED FOR THE HYPERBARIC
 AND OXYGEN ROOMS.
  
 4) P.3: REFER TO SECTIONS 14.2.1.4- 14.2.1.5 NFPA 99-
 VERIFY THE MEDICAL OXYGEN SYSTEM MEETS ALL THE
 REQUIREMENTS FOR PIPING AND STORAGE OF THE OXYGEN.
  
 5) M.1: A FIRE DAMPER IS REQUIRED FOR THE WALL DIFFUSER
 PENETRATING THE FIRE-RATED OYXGEN ROOM WALL- SECTION
 607.5.2 FBC M.
  
 6) LS.1, M.1, P.3: REFER TO TABLE 307.1(1) FBC B- THE
 OXYGEN ROOM IS CLASSIFIED AS AN H-3 OCCUPANCY BASED ON
 THE 20, 048 CU. FT. OF OXYGEN BEING STORED IN THE ROOM.
 PLEASE SEE SECTION 510.1 FBC M. AND PROVIDE A HAZARDOUS
 EXHAUST SYSTEM FOR THE ROOM. SHOW THE EXHAUST DUCT RUN,
 TYPE OF DUCT TO BE USED, AND TERMINATION LOCATION- SEE
 SECTIONS 510.4, 510.6.5, 510.6.7, 510.7, AND 510.9 FBC
 M. A) PROVIDE A ROOF PLAN SHOWING THE LOCATION OF THE
 FAN AND CLEARANCE DISTANCES IN ACCORDANCE WITH SECTION
 501.3.1 FBC M, AND IN ACCORDANCE WITH SECTION 304.11-
 MINIMUM 10' TO ROOF EDGE OR PROVIDE A GUARD. A) REFER
 TO SECTION 9.3.6.5.3 FOR MECHANICAL VENTILATION RATE,
 LOCATION OF EXHAUST INLETS, AND REQUIRED CONTINOUS
 OPERATION- REMOVE THE THERMOSTAT FROM THE PLAN. B)
 PROVIDE A FL. PRODUICT APPROVAL AND/OR MIAMI-DADE NOA
 FOR THE MAKEUP AIR LOUVER IN THE OXYGEN ROOM- SECTION
 9N-03 FAC. THE LOUVER SHALL BE AMCA 550 RATED )401.5
 FBC M), AND MAY REQUIRED A FIRE DAMPER IF IT IS
 DETERMINED THE EXTERIOR WALL HAS TO BE FIRE-RATED.
  
 7) LS.1: THE WALLS ENCLOSING THE OXYGEN ROOM MUST BE
 3-HR FIRE-RESISTANT IN ACCORDANCE WITH TABLE 508.4 FBC
 B.
  
 8) M.1: PROVIDE EQUIPMENT SCHEDULES FOR THE NEW AC
 SYSTEMS, AND SHOW THE LOCATIONS OF THE NEW CONDENSERS-
 TABLE C403.2.3(1) AND SECTION C501.7 FBC EC, AND
 SECTION 107.2.1 WPB.
  
 9) M.1: PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE CONDENSERS AND ROOF FANS- SECION 301.15 FBC M.
  
 10) M.1: PROVIDE CONDENSATE DISPOSAL PLANS FOR THE NEW
 SYSTEMS- SECTION 307.2.1 FBC M.
  
 11) M.1, P.3: SUBMIT PRODUCT DATA SHEETS FOR THE
 HYPERBARIC CHAMBERS- SECTION 304.1 FBC M.
  
 12) M.1, P.3: REFER TO SECTION 5.1.3.1.1 & 5.1.3.1.2-
 PROVIDE PRODUCT SPECIFICATION SHEETS FOR THE OXYGEN
 TANKS AND CYLINDERS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved