2019-03-18 10:46:09PERMIT # 19030507
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) SHEET T.1 INDICATES THAT THIS BUILDING IS NOT
 CURRENTLY EQUIPPED WITH A FIRE SPRINKLER SYSTEM.
 HOWEVER, SHEET LS.1 (LIFE SAFETY) IDENTIFIES THAT A
 FIRE SPRINKLER SYSTEM WILL BE INSTALLED FOR COVERAGE IN
 ROOMS 128 & 129, ONLY.
 BECAUSE THIS BUILDING DOES NOT CURRENTLY HAVE FIRE
 SPRINKLER SYSTEM INSTALLED, ENGINEERED FIRE ALARM AND
 FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR
 A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 2) PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE