| 2019-03-18 10:46:09 | PERMIT # 19030507 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FAILED COMMENTS: | | | | | | 1) SHEET T.1 INDICATES THAT THIS BUILDING IS NOT | | | CURRENTLY EQUIPPED WITH A FIRE SPRINKLER SYSTEM. | | | HOWEVER, SHEET LS.1 (LIFE SAFETY) IDENTIFIES THAT A | | | FIRE SPRINKLER SYSTEM WILL BE INSTALLED FOR COVERAGE IN | | | ROOMS 128 & 129, ONLY. | | | BECAUSE THIS BUILDING DOES NOT CURRENTLY HAVE FIRE | | | SPRINKLER SYSTEM INSTALLED, ENGINEERED FIRE ALARM AND | | | FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR | | | A GENERAL BUILDING PERMIT. | | | AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE | | | SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS | | | (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) | | | FOR A SUB-PERMIT. | | | | | | 2) PER FLORIDA ADMINISTRATIVE CODE SECTION | | | 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS | | | SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER | | | SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE | | | TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR | | | EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN | | | DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT | | | FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION | | | SUCH AS PRE-ENGINEERED SYSTEMS. | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|