| 2019-04-22 07:08:24 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC |
| | 215.5; WPB FBC 107.2.1 |
| | |
| | 2. PROVIDE ITEMIZED LOAD CALCULATION SHOWING THE TOTAL |
| | CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS, THE |
| | METHOD USED FOR DEMAND FACTORS, AND THE CALCULATED LOAD |
| | AFTER APPLYING DEMAND FACTORS. FBC 107.2.1 NEC 220. |
| | |
| | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL NEC 110.9, 110.10 |
| | |
| | 4. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL FOR ALL |
| | SPECIAL EQUIPMENT. HYPERBARIC CHAMBER, OXYGEN |
| | DISPENSING MACHINES ETC. FBC 107.2.1 NEC 90.7, 110.2, |
| | 110.3B |
| | |
| | 5. ARE THERE ANY CLASSIFIED LOCATIONS/ZONES? PLEASE |
| | PROVIDE DOCUMENTATION STATING WHETHER THERE IS OR IS |
| | NOT. FBC 107.2.1. |
| | |
| | 6. VALUE FOR AMOUNT OF WORK SHOWN APPEARS LOW. PROVIDE |
| | COPY OF SIGNED CONTRACT (SIGNED BY BOTH OWNER AND |
| | CONTRACTOR). |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |