Plan Review Notes
Plan Review Notes For Permit 19030507
Permit Number 19030507
Review Stop B
Sequence Number 1
Notes
Date Text
2019-05-07 11:29:10****CORRECTIONS****
 W.P.B. PERMIT: 19030507
 REVIEWED: MAY 6, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3
 SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
  - WHICH METHOD IS BEING USED FOR COMPLIANCE?
 (PRESCRIPTIVE,WORK AREA OR PERFORMANCE)
  
 2) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVAL FOR
 EXTERIOR DOORS, OR INDICATE THAT THEY WILL BE A
 DEFERRED SUBMITTAL.
  
 3) 425.1 HYPERBARIC FACILITIES. HYPERBARIC FACILITIES
 SHALL MEET
 THE REQUIREMENTS CONTAINED IN CHAPTER 14 OF NFPA 99.
 (NO RESPONSE REQUIRED)
  
 4) 451.3.4.1 NO DOORS SHALL SWING INTO THE CORRIDOR
 EXCEPT
 THOSE TO SMALL CLOSETS OR SMALL MECHANICAL OR
 ELECTRICAL
 ROOMS THAT CANNOT BE USEFULLY OCCUPIED WITH THE DOORS
 IN THE CLOSED POSITION.
  -VERIFY SWING OF DOOR 101
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  