| Date |
Text |
| 2019-04-03 12:35:58 | PERMIT # 19030479 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | FAILED COMMENTS: |
| | |
| | 1) THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY. |
| | INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE |
| | (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.3 |
| | OF NFPA 101 FLORIDA EDITION 2015. FOR NON-SEPARATED |
| | MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE |
| | SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO |
| | THE BUILDING. |
| | MORE SPECIFICALLY, THE AREA LABELED "COVERED PLATFORM" |
| | WAS PREVIOUSLY DISCUSSED IN A PRIOR MEETING AND WAS |
| | IDENTIFIED AS AN AREA THAT COULD AND WOULD BE USED FOR |
| | PRESENTATIONS, DEMONSTRATIONS, AND PERFORMANCES, |
| | THEREFORE IT WOULLD FALL UNDER THE REQUIREMENTS OF AN |
| | ASSEMBLY OCCUPANCY. |
| | |
| | 2) IDENTIFY AND LABEL ALL OF THE FIRE RATED |
| | SEPARATIONS, INCLUDING THE LEVEL OF SEPARATION (1 HOUR |
| | OR 2 HOUR RATED). THIS SHOULD INCLUDE ALL RATED WALLS, |
| | FLOORS, AND CEILINGS. |
| | |
| | 3) PLEASE PROVIDE A NARRATIVE EXPLAINING WHAT IS BEING |
| | STORED AND HOW. WHAT IS THE CLASSIFICATION OF HAZARD OF |
| | CONTENTS BEING STORED, HOW MUCH MATERIAL IS BEING |
| | STORED, AND HOW WILL IT BE STORED (RACKS, PALLETS, |
| | ETC.). |
| | PER NFPA 101, CHAPTER 6: |
| | 6.2.2 CLASSIFICATION OF HAZARD OF CONTENTS. |
| | 6.2.2.1* GENERAL. THE HAZARD OF CONTENTS OF ANY |
| | BUILDING OR STRUCTURE SHALL BE CLASSIFIED AS LOW, |
| | ORDINARY, OR HIGH IN ACCORDANCE WITH 6.2.2.2, 6.2.2.3, |
| | AND 6.2.2.4. |
| | |
| | 4) AT PRESENT THE COVERED PATIO IS INTENDED TO BE USED |
| | AS AN ASSEMBLY OCCUPANCY FOR DEMONSTRATIONS AND |
| | PRESENTATIONS, AS SUCH IT SHALL HAVE TWO (2) MEANS OF |
| | EGRESS AS REQUIRED UNDER NFPA 101, CHAPTERS 7 AND 12. |
| | CURRENTLY, THERE APPEARS TO ONLY BE ONE MEANS OF EGRESS |
| | PROVIDED. |
| | |
| | 5) IT APPEARS THAT ONLY THE ARCHITECTURAL DRAWINGS |
| | LISTED UNDER THE INDEX ON THE COVER SHEET HAVE BEEN |
| | PROVIDED. |
| | |
| | 6) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION |
| | SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS |
| | MAY BE GENERATED DURING PLAN RESUBMISSION. |
| | |
| | |
| | SUE ELLEN CALDERON |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | |