2019-03-12 09:15:12PERMIT #19030476
 FIRE REVIEW COMMENTS
  
 FAIL COMMENTS:
  
 1) THE OCCUPANT LOAD FOR THE 40 X 100 TENT SHALL COMPLY
 WITH THE OCCUPANT LOAD FACTOR AS LISTED UNDER NFPA 101:
 CHAPTER 7, TABLE 7.3.1.2. MORE SPECIFICALLY, ASSEMBLY
 USE: LESS CONCENTRATED USE, WITHOUT FIXED SEATING - 15
 SQ FT/PERSON.
 BASED ON THE INFORMATION PROVIDED AND THE SEATING
 ARRANGEMENT THAT INDICATES 120 PERSONS, THE OCCUPANT
 LOAD IS BEING EXCEEDED FOR THIS SIZE TENT.
  
 2) 1)SEATING SHALL BE ARRANGED IN A MANNER THAT
 COMPLIES WITH THE AISLE AND AISLEWAY REQUIREMENTS AS
 LISTED UNDER NFPA 101: 12.2.5 (ARRANGEMENT OF MEANS OF
 EGRESS).
  
 3) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE