2019-04-02 08:48:032017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19030471 - OPERATING ROOM # 8
 ADD: 901 45TH ST.
 CONT: WESTBROOKE CORP.
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. APRIL 02/ 2019
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE REMOVAL OF
 SUSPENDED CEILINGS & INSTALL NEW DRYWALL CEILINGS IN
 THE OPERATING ROOM # 8. THE PLANS INCLUDE A LIFE SAFETY
 SHEET, TEMPORARY ZIP WALL CONTAINMENT BARRIER, AND
 SHEET A3.1 THE REFLECTED CEILING PLAN.
 PLEASE NOTE ON SHEET A3.1 THERE IS A CHART FOR STUD
 SCHEDULE (VERTICAL APPLICATION) NO MENTION OF A
 HORIZONTAL USE OF STUDS FOR CEILING FRAMING.
 MISSING FROM THE PLANS ARE THE DESIGN CRITERIA FOR
 CEILING SPANS AND THICKNESS OF THE FINISH MATERIALS:
  
 2017 FBC-B TABLE 2508.1 STEEL FRAMING FOR GYPSUM BOARD.
  
 1A) SUSPENDED CEILING, SPACING OF HANGER WIRE, DIAMETER
 OF HANGER WIRE, ANCHORAGE TO DECK ABOVE, TYPE OF
 HORIZONTAL CHANNEL, BLACK IRON OR GAL.-STEEL, SIZE AND
 GAUGE OF STEEL, IF HI-HAT CHANNEL (RIGID FURRING
 CHANNEL) IS TO BE USED, SIZE GAUGE, AND SPACING,
 SCREWED OR SADDLE TIED SIMPLE SPAN OR MULTIPLE SPANS,
 AND THE TOTAL UNIFORM LOAD.
  
 1B) SSMA ICBO ER-4943P CEILING SPAN TABLES, FOR STEEL
 STUDS, SECTION (SIZE), THICKNESS (MIL), SPACING, LIVE
 LOADS, DEFLECTION, UNSUPPORTED SPAN, SUPPORTED
 MID-SPAN, SCREW SIZE AND SPACING FOR FRAMING MEMBERS
 AND TO GYPSUM.
  
 1C) 2017 FBC-B TABLE 1604.3 DEFLECTION LIMITATION.
  
 1D) THE THICKNESS OF THE CEILING GYPSUM WALLBOARD
 CEILING WILL BE NEEDED FOR THE SPAN TABLES, IF SINGLE
 LAYER APPLICATION IS TO BE INSTALLED. 2017 FBC-B
 2508.3.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved