| Plan Review Notes For Permit 19030461 |
| Permit Number |
19030461 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-04-11 14:22:47 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THERE ARE NO INDICATIONS OF AN EXISTING FIRE | | | SPRINKLER SYSTEM OVER THE BAR AREA. | | | | | | THE PROPOSED CANOPY WOULD OBSTRUCT THE EXISTING FIRE | | | SPRINKLER COVERAGE. ADDITIONALL FIRE SPRINKLERS WOUD | | | NEED TO BE EXTENDED TO UNDER THE PROPOSED THROUGH | | | SEPARATE PERMIT AND SHOP DRAWINGS. | | | | | | PLEASE REVIEW AND PROVIDE EXISTING FIRE SPRINKLER | | | LOCATION DETAILS AND PROVIDE AN APPLICABLE NOTE . | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|