| 2019-03-28 18:38:29 | RESIDENTIAL (R3) INTERIOR DEMOLITION PERMIT, BUILDING |
| | REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- SHEET 1 OF 2 SUBMITTED WAS SIGNED AND SEALED BY A |
| | FLORIDA REGISTERED ARCHITECT. ARCHITECT NEED TO PROVIDE |
| | A TITLE BLOCK WITH ALL THE INFORMATION REQUIRED BY SEC. |
| | 61G-16.004 FAC. |
| | |
| | 2- MISSING SHEET 2 OF 2 AS NOTED ON NOTE LOCATED ON THE |
| | TOP OF SHEET 1 OF 2 SUBMITTED. PROVIDE COMPLETE |
| | DRAWINGS. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- PERMIT APPLICATION SUBMITTED IS "TO DEMO THE |
| | EXISTING AREA THAT WERE NOT PERMITTED ORIGINALLY". THIS |
| | PERMIT IS FOR INTERIOR DEMOLITION ONLY NOT FOR |
| | CONSTRUCTION. COORDINATE WITH THE ELECTRICAL AND |
| | PLUMBING TRADES FOR CAPPING OF LINES. NEED PERMIT |
| | APPLICATION AND PLANS FOR ANY PROPOSED WORK. SEC. 105.1 |
| | CITY AMENDMENTS. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |