| 2019-04-04 17:33:35 | ***CORRECTIONS*** |
| | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 2ND PLAN REVIEW DENIED: |
| | R301.1APPLICATION. |
| | BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF, SHALL |
| | BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING |
| | DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS, SNOW |
| | LOADS, WIND LOADS AND SEISMIC LOADS AS PRESCRIBED BY |
| | THIS CODE. THE CONSTRUCTION OF BUILDINGS AND STRUCTURES |
| | IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL |
| | RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH |
| | THAT MEETS ALL REQUIREMENTS FOR THE TRANSFER OF ALL |
| | LOADS FROM THEIR POINT OF ORIGIN THROUGH THE |
| | LOAD-RESISTING ELEMENTS TO THE FOUNDATION. BUILDINGS |
| | AND STRUCTURES CONSTRUCTED AS PRESCRIBED BY THIS CODE |
| | ARE DEEMED TO COMPLY WITH THE REQUIREMENTS OF THIS |
| | SECTION. |
| | |
| | FBC B 107. THE SUBMITTED PLANS ARE MISSING NECESSARY |
| | INFORMATION, SUCH AS: |
| | |
| | 1.SITE BUILT REQUIREMENTS: |
| | A. PROVIDE FOUNDATION PLAN ? FOOTINGS/SLAB ON |
| | GRADE/REINFORCING |
| | B. PROVIDE BUILDING PLANS: |
| | 1. FLOOR: LIVE LOADS, CONNECTION DETAILS, FOUNDATION |
| | DETAILS, & COMPACTION REQUIREMENTS. |
| | 2. WALLS: WIND LOADS, BRACING, AND CONNECTION DETAILS. |
| | PLEASE CLARIFY: THE PROPOSED BATHROOM APPEARS TO BE |
| | COVERING UP AN EXISTING WINDOW AND THE EXISTING REAR |
| | WALL APPEARD TO SHOW A NEW SLIDING GLASS DOOR. |
| | 3. ROOF FRAMING: DEAD LOADS, WIND LOADS, UPLIFT |
| | CAPACITIES; RAFTER SPACING IS QUESTIONABLE CONSIDERING |
| | SPAN AND TYPICAL GRADES, ROOF FRAMING TO WALL |
| | CONNECTIONS, |
| | C. WINDOW AND/OR DOOR SCHEDULE WITH ROUGH OPENINGS AND |
| | DESIGN WIND LOADS. |
| | D. PRODUCT APPROVALS FOR ALL ROOFING, WINDOWS AND/OR |
| | DOORS. |
| | E. PROVIDE SITE PLAN WITH SETBACKS FROM PROPERTY LINES. |
| | |
| | 2. ROOFING: |
| | A. ROOFING SUB-PERMIT IS REQUIRED: |
| | B. PROVIDE ALL RELATED PRODUCT APPROVALS AND IDENTIFY |
| | SYSTEMS TO BE USED. |
| | C. PROVIDE DESIGN WIND LOADS FOR ZONE 1, 2, & 3. |
| | D. PROVIDE SIGNED AND SEALED CALCULATIONS FOR ZONES 2 & |
| | 3 PER RAS 117 OR FM LPDS 1-52. |
| | |
| | 3. SEPERATE PERMITS REQUIRED: |
| | A. ELECTRIC |
| | B. PLUMBING |
| | |
| | 4. VALUATION: |
| | THE VALUATION OF THIS PERMIT APPLICATION APPEARS TO BE |
| | VERY LOW IN COMPARISON TO SOURCES SUCH AS THE ICC |
| | BUILDING VALUATION DATA. PLEASE RE-EVALUATE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY |
| | RESULT IN NEW PLAN REVIEW COMMENTS. |