Plan Review Notes
Plan Review Notes For Permit 19030441
Permit Number 19030441
Review Stop B
Sequence Number 2
Notes
Date Text
2019-04-04 17:33:35***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND PLAN REVIEW DENIED:
 R301.1APPLICATION.
 BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF, SHALL
 BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING
 DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS, SNOW
 LOADS, WIND LOADS AND SEISMIC LOADS AS PRESCRIBED BY
 THIS CODE. THE CONSTRUCTION OF BUILDINGS AND STRUCTURES
 IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 THAT MEETS ALL REQUIREMENTS FOR THE TRANSFER OF ALL
 LOADS FROM THEIR POINT OF ORIGIN THROUGH THE
 LOAD-RESISTING ELEMENTS TO THE FOUNDATION. BUILDINGS
 AND STRUCTURES CONSTRUCTED AS PRESCRIBED BY THIS CODE
 ARE DEEMED TO COMPLY WITH THE REQUIREMENTS OF THIS
 SECTION.
  
 FBC B 107. THE SUBMITTED PLANS ARE MISSING NECESSARY
 INFORMATION, SUCH AS:
  
 1.SITE BUILT REQUIREMENTS:
 A. PROVIDE FOUNDATION PLAN ? FOOTINGS/SLAB ON
 GRADE/REINFORCING
 B. PROVIDE BUILDING PLANS:
 1. FLOOR: LIVE LOADS, CONNECTION DETAILS, FOUNDATION
 DETAILS, & COMPACTION REQUIREMENTS.
 2. WALLS: WIND LOADS, BRACING, AND CONNECTION DETAILS.
 PLEASE CLARIFY: THE PROPOSED BATHROOM APPEARS TO BE
 COVERING UP AN EXISTING WINDOW AND THE EXISTING REAR
 WALL APPEARD TO SHOW A NEW SLIDING GLASS DOOR.
 3. ROOF FRAMING: DEAD LOADS, WIND LOADS, UPLIFT
 CAPACITIES; RAFTER SPACING IS QUESTIONABLE CONSIDERING
 SPAN AND TYPICAL GRADES, ROOF FRAMING TO WALL
 CONNECTIONS,
 C. WINDOW AND/OR DOOR SCHEDULE WITH ROUGH OPENINGS AND
 DESIGN WIND LOADS.
 D. PRODUCT APPROVALS FOR ALL ROOFING, WINDOWS AND/OR
 DOORS.
 E. PROVIDE SITE PLAN WITH SETBACKS FROM PROPERTY LINES.
  
 2. ROOFING:
 A. ROOFING SUB-PERMIT IS REQUIRED:
 B. PROVIDE ALL RELATED PRODUCT APPROVALS AND IDENTIFY
 SYSTEMS TO BE USED.
 C. PROVIDE DESIGN WIND LOADS FOR ZONE 1, 2, & 3.
 D. PROVIDE SIGNED AND SEALED CALCULATIONS FOR ZONES 2 &
 3 PER RAS 117 OR FM LPDS 1-52.
  
 3. SEPERATE PERMITS REQUIRED:
 A. ELECTRIC
 B. PLUMBING
  
 4. VALUATION:
 THE VALUATION OF THIS PERMIT APPLICATION APPEARS TO BE
 VERY LOW IN COMPARISON TO SOURCES SUCH AS THE ICC
 BUILDING VALUATION DATA. PLEASE RE-EVALUATE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.