| 2019-03-14 10:25:53 | PERMIT # 19030437 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | APPROVED PROVISO: |
| | |
| | 1) CUT SHEETS / MANUFACTURER'S SPECS SHALL BE PROVIDED |
| | TO THE FIRE INSPECTOR AT THE TIME OF INSPECTION AND |
| | SHALL BE MADE READILLY AVAILABLE ON-SITE AT ALL TIMES. |
| | FAILURE TO PROVIDE THESE DOCUMENTS WILL RESULT IN A |
| | FAILED INSPECTION. |
| | |
| | 2) JOINT RESTRAINT: PER NFPA 13 & 24, SECTION 10.8.1.1, |
| | ALL TEES, PLUGS, CAPS, BENDS, REDUCERS, VALVES, AND |
| | HYDRANT BRANCHES SHALL BE RESTRAINED AGAINST MOVEMENT |
| | BY USING THRUST BLOCKS OR RESTRAINED JOINT SYSTEMS. |
| | |
| | 3) CORROSION RESISTANCE: PER NFPA 13 & 24, SECTION |
| | 10.8.3.5, AFTER INSTALLATION, RODS, NUTS, BOLTS, |
| | WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES SHALL BE |
| | CLEANED AND THOROUGHLY COATED WITH A BITUMINOUS OR |
| | OTHER ACCEPTABLE CORROSION-RETARDING MATERIAL. |
| | |
| | 4) ACCEPTANCE REQUIREMENTS: PER NFPA 13 & 24, SECTION |
| | 10.10.2.1.3, UNDERGROUND PIPING, FROM THE WATER SUPPLY |
| | TO THE SYSTEM RISER, AND LEAD-IN CONNECTIONS TO THE |
| | SYSTEM RISER SHALL BE COMPLETELY FLUSHED BEFORE |
| | CONNECTION IS MADE TO DOWNSTREAM FIRE PROTECTION SYSTEM |
| | PIPING. THE MINIMUM RATE OF FLOW SHALL BE NOT LESS THAN |
| | THE FLOW NECESSARY TO PROVIDE A VELOCITY OF 10 FEET PER |
| | SECOND. |
| | |
| | 5) FLUSHING PAPERS: PER NFPA 13 & 24, SECTION 10.10.1, |
| | THE INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR THE |
| | COMPLETING AND SIGNING THE CONTRACTOR?S MATERIAL AND |
| | TEST CERTIFICATE(S) SHOWN IN FIGURE 10.10.1. |
| | |
| | 6) HYDROSTATIC TESTING: PER NFPA 13 & 24, SECTION |
| | 10.10.2.2.1 ALL PIPING AND ATTACHED APPURTENANCES |
| | SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE |
| | HYDROSTATICALLY TESTED AT |
| | 200 PSI OR 50 PSI IN EXCESS OF THE SYSTEM WORKING |
| | PRESSURE, WHICHEVER IS GREATER, AND SHALL MAINTAIN THAT |
| | PRESSURE +/-5 PSI FOR 2 HOURS. |
| | |
| | 7) THIS IS A CONDITIONAL APPROVAL. COMPLIANCE WITH THE |
| | ABOVE CONDITIONS WILL BE VERIFIED AT THE TIME OF |
| | INSPECTION. FAILURE TO MEET THE CONDITIONS WILL RESULT |
| | IN A FAILED INSPECTION. |
| | |
| | |