| 2019-06-20 16:43:57 | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | ****NEED ENERGY CALCULATIONS TO BE PROPERLY SIGNED BY |
| | THE OWNER AND ALL PLANS NEED THE ENGINEER'S SEAL AND |
| | SIGNATURE BEFORE APPROVAL. |
| | |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | SEC. R401.3 FBC-RESIDENTIAL (DRAINAGE). |
| | SEC. 107.2.5 CITY AMENDMENTS (SITE PLAN). |
| | SEC. 110.9 CITY AMENDMENTS (IMPACT OF CONSTRUCTION). |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 2- OK. |
| | |
| | 3-OK |
| | |
| | ORIGINAL COMMENT: |
| | 4- A)DESIGN PRESSURES SHOWN FOR NEW MASTER BEDROOM |
| | DOUBLE DOORS AND NEW FAMILY ROOM SINGLE DOOR DON'T |
| | CORRESPOND TO THE EFFECTIVE WIND AREA SHOWN ON |
| | COMPONENTS AND CLADDING DESIGN PRESSURES ON SHEET 5.1. |
| | REVISE AS REQUIRED. SEE SIZE OF DOORS AND REVISE AS |
| | REQUIRED. |
| | |
| | RESPONSE: |
| | PARTIALLY ADDRESSED. THE DOUBLE DOORS ARE CORRECT BUT |
| | SINGLE DOOR IS NOT. THE LOADS FOR SINGLE DOOR "01" NEED |
| | TO BE REVISED. NEED TO USE DESIGN PRESSURES FOR THE |
| | LOWER EFFECTIVE AREA AS REQUIRED BY FOOTNOTE "B" OF |
| | TABLE R301.2(2)FBC-RESIDENTIAL. SEE TABLE FOR DESIGN |
| | PRESSURES OF 20S.F. EFFECTIVE WIND AREA AND REVISE AS |
| | REQUIRED. REMEMBER THAT DESIGN PRESSURES ON THIS TABLE |
| | NEED TO BE ADJUSTED WITH THE EXPOSURE AND HEIGHT |
| | COEFFICIENT OF TABLE R301.2(3) FBC-RESIDENTIAL. |
| | |
| | ORIGINAL COMMENT: |
| | B) GARAGE DOORS DESIGN PRESSURES SHOWN ON THE |
| | COMPONENTS AND CLADDING DESIGN PRESSURES ON SHEET 5.1 |
| | DON'T CORRESPOND TO THE ONES SHOWN ON TABLE 301.2(4) |
| | FBC-RESIDENTIAL WHEN MULTIPLIED BY THE COEFFICIENT FOR |
| | EXPOSURE "C". SEE TABLE R301.2(3) FBC-RESIDENTIAL AND |
| | REVISE AS REQUIRED. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 5- ENERGY CALCULATIONS SUBMITTED: |
| | ORIGINAL COMMENT: |
| | A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE |
| | CERTIFIED AT THE BOTTOM BY THE OWNER OR OWNER'S LEGALLY |
| | DESIGNATED AGENT AS REQUIRED BY SEC. R103.1.1.2 |
| | FBC-ENERGY CONSERVATION, 6TH EDITION (2017). |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | B)OK. |
| | |
| | C) OK. |
| | |
| | D) OK. |
| | |
| | E) OK. |
| | |
| | ORIGINAL COMMENT: |
| | 6- ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING IN |
| | THE CONSTRUCTION DOCUMENTS. SEC. 107.2.1.1 CITY |
| | AMENDMENTS. IF SPECIFYING ROOF TILE ADHESIVE, THEN |
| | SPECIFY PADDY SIZE AND PROVIDE PRODUCT APPROVAL. IF |
| | SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE AND NUMBER |
| | OF SCREWS. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 7-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. CONTRACTOR TO ADVICE IF SUBMITTING THIS |
| | INFORMATION LATER). |
| | |
| | ORIGINAL COMMENT: |
| | A)WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED: |
| | CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY |
| | COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | B)FIXED WINDOWS. PROVIDE FLORIDA PRODUCT APPROVAL COVER |
| | PAGE THAT CORRESPONDS TO DRAWINGS SUBMITTED. COVER PAGE |
| | SUBMITTED IS FOR MANY DIFFERENT PRODUCT APPROVAL |
| | NUMBERS. UNABLE TO IDENTIFY THE ONE THAT CORRESPONDS TO |
| | DRAWING SUBMITTED. |
| | |
| | RESPONSE: |
| | PARTIALLY DONE. PROVIDE COMPLETE INFORMATION. PROVIDE |
| | FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO |
| | DRAWINGS SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | C) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF |
| | RECORD. SEE ROOF TILE NOA SUBMITTED FOR LISTED |
| | ADHESIVES. AND CLEARLY MARK PADDY SIZE AS REQUIRED BY |
| | CITY POLICY FOR ALL ROOFING PERMITS. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | D) DOUBLE DOORS AS SHOWN FOR NEW STORAGE. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 |
| | CITY AMENDMENTS |
| | |
| | 9- OK. |
| | |
| | 10- OK. |
| | |
| | NEW COMMENT: |
| | 11- ALL PLANS ON BOTH SETS NEED TO HAVE THE SEAL AND |
| | SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY |
| | CHAPTER 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR |
| | PUBLIC RECORDS. |
| | |
| | |
| | 12- WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | RESPONSE: |
| | ORIGINAL PLANS AND SUBMITTALS (ENERGY CALCULATIONS) |
| | WERE NOT RE-SUBMITTED. IN THE FUTURE PLEASE RES-SUBMIT |
| | EVERYTHING THAT WAS REVIEWED IN ORDER TO USE THEM FOR |
| | REFERENCE AND EXPEDITE THE REVIEW PROCESS. |
| | |
| | EVEN THOUGH RESPONSE LETTER IS NOT MANDATORY IT IT'S |
| | VERY HELPFUL TO PROVIDE ONE IN ORDER TO TO EXPEDITE THE |
| | REVIEW PROCESS. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |