| 2019-05-24 09:46:59 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| | SATISFACTORILY ARE LISTED BELOW, THE SAME PLAN WAS |
| | SUBMITTED WITH NO CHANGES. |
| | |
| | 1. SHOW ON PANEL SCHEDULE AND PLAN ALL REQUIRED |
| | ARC-FAULT CIRCUITS REQUIRED BY 210.12 NEC 2014. AFCI |
| | NEEDED FOR DISHWASHER AND DISPOSAL, KITCHEN SMALL |
| | APPLIANCE CIRCUITS, LAUNDRY ROOM LIGHTING AND |
| | RECEPTACLES, ETC. NEC 210.12 |
| | |
| | 2. SMOKE ALARM/ CARBON MONOXIDE DETECTOR COMBO REQUIRED |
| | WITHIN 10' OUTSIDE OF BEDROOM DOOR. PROVIDE CORRECTION. |
| | FBC 314&315 |
| | |
| | 3. RECEPTACLES REQUIRED AT BOTH FRONT AND REAR OF |
| | DWELLING. NEC 210.52E1 |
| | |
| | 4. PROVIDE NOTE ON PLAN STATING "PROVIDE COMPLIANCE: "A |
| | MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| | LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH |
| | EFFICACY LAMPS". A NOTE WILL SUFFICE. FBC EC R404.1" |
| | |
| | 5. DISHWASHER MUST BE GFCI PROTECTED. NEC 210.8D |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |