| Notes |
| Date |
Text |
| 2019-05-13 08:12:05 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 107, THE PRODUCT APPROVALS IS TO BE REVIEWED BY | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL. | | | | | | 2. FS471, THE ROOF PLAN IS TO BE CONSISTENT WITH DESIGN | | | CRITERIA SPECIFIED BY SEOR. SEOR TO REVIEW PLAN PRIOR | | | TO SUBMITTAL. | | | | | | 3. FBC B 1609, THE DESIGN PRESSURES SPECIFIED BY THE | | | ROOF ENGINEER FOR ENHANCED FASTENING FOR ZONES 1 AND 2 | | | EXCEED THE DESIGN PRESSURES SPECIFIED BY SEOR SO ARE | | | ACCEPTABLE (-86.18, -135.27). | | | | | | HOWEVER, ZONE 3 FOR THIS SUBMITTAL ( -135.27) IS LESS | | | THAN -180.84 PSF SPECIFIED ON SHEETS S0-01 AND S0-05. | | | | | | | | | |
|