Plan Review Notes
Plan Review Notes For Permit 19030354
Permit Number 19030354
Review Stop B
Sequence Number 1
Notes
Date Text
2019-05-13 08:12:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, THE PRODUCT APPROVALS IS TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 2. FS471, THE ROOF PLAN IS TO BE CONSISTENT WITH DESIGN
 CRITERIA SPECIFIED BY SEOR. SEOR TO REVIEW PLAN PRIOR
 TO SUBMITTAL.
  
 3. FBC B 1609, THE DESIGN PRESSURES SPECIFIED BY THE
 ROOF ENGINEER FOR ENHANCED FASTENING FOR ZONES 1 AND 2
 EXCEED THE DESIGN PRESSURES SPECIFIED BY SEOR SO ARE
 ACCEPTABLE (-86.18, -135.27).
  
 HOWEVER, ZONE 3 FOR THIS SUBMITTAL ( -135.27) IS LESS
 THAN -180.84 PSF SPECIFIED ON SHEETS S0-01 AND S0-05.
  
  
  