| Plan Review Notes For Permit 19030292 |
| Permit Number |
19030292 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-03-11 14:06:51 | PLUMBING 1ST REVIEW**DENIED** THIS UNIT WAS CONSTRUCTED | | | UNDER THE FAIR HOUSING ACT (F.A.C) | | | | | | 1) THE REMOVAL OF THE EXISTING TUB AND CONVERTING IT TO | | | A SHOWER IS NOT PERMITTED UNDER F.A.C WITH OUT A | | | COMPLETE PLAN BEING PROVIDE SHOWING ALL USABLE BATHROOM | | | AND KNOWING WHAT DESIGN SPEC WAS USED. FOR SHOWERS | | | UNDER F.A.C YOU MUST SHOW AND HAVE A 48" X 30" PARALLEI | | | APPROACH TO THE SHOWER WHICH THE TOILET IS NOT | | | PERMITTED TO ENCROACH INTO. THE TOILET MUST KEEP THE | | | 18" CLEARANCE FROM THE TUB/SHOWER. I WOULD ADVISED | | | CONSULTING A DESIGN PROFESSIONAL WITH FAIR HOUSING | | | KNOWLEDGE. | | | | | | 2) PLANS ARE NOT PERMITTED TO BE DRAWN IN PENCIL. PLANS | | | MUST BE ON SUITABLE MATERIAL. FBC 107.2.1 | | | | | | 3) PROVIDE A PLAN SHOWING THE REQUIRED F.A.C CLEAR | | | FLOOR SPACES WILL REMAIN. FBC 107.3.5 | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | 561-248-2703 | | | | | | SAMANTHA HILL | | | CHIEF PLANS EXAMINER | | | 561-805-6724 |
|